EasyManua.ls Logo

Hitachi RPC-6.0FSN3E - 10.3.1 Cable sizes; 10.3.2 Main breaker switch

Hitachi RPC-6.0FSN3E
756 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.3.1 Cable sizes
Field minimum wire sizes for power source and transmission
Model Power supply
Maximum
running current
(A)
Power source cable size  Transmitting cable size
Earth wire size
(mm
2
)
EN60 335-1
(1)
*1
(mm
2
)
EN60 335-1
(1)
*1
(mm
2
)
RAS-8FSXN1E
3N~ 400V/50Hz
15.0 4.0 0.75 4.0
RAS-10FSXN1E 20.0 6.0 0.75 6.0
RAS-12FSXN1E 26.5 6.0 0.75 6.0
RAS-14FSXN1E 29.2 10.0 0.75 10.0
RAS-16FSXN1E 33.0 10.0 0.75 10.0
RAS-5FSXNH(E)
3N~ 400V/50Hz
13.0 4.0 0.75 4.0
RAS-6FSXNH(E) 13.0 4.0 0.75 4.0
RAS-8FSXNH(E) 15.0 4.0 0.75 4.0
RAS-10FSXNH(E) 18.7 6.0 0.75 6.0
RAS-12FSXNH(E) 20.0 6.0 0.75 6.0
* Refer to the NOTES for selection of the power source cable size.
(1)
The cross-sections of the cable should be selected for the maximum current of the unit, in accordance with European Standard
EN60 335-1.
NOTE
Do not use cables that are lighter than the normal exible coated polychloroprene cable (code H05RN-F).
10.3.2 Main breaker switch
Electrical data and recommended wiring, breaker size/1 outdoor unit
Model Power supply
Maximum
running
current
(A)
Power supply
line type
ELB Main switch
CB
(A)
Nominal
current
(A)
Nominal sensitive
current
(mA)
Nominal current
(A)
RAS-8FSXN1E
3N~ 400V/50Hz
15.0 MLFC 2.0SQ 40 30 20 20
RAS-10FSXN1E 20.0 MLFC 3.5SQ 40 30 30 30
RAS-12FSXN1E 26.5 MLFC 5.5SQ 40 30 40 40
RAS-14FSXN1E 29.2 MLFC 5.5SQ 63 30 40 40
RAS-16FSXN1E 33.0 MLFC 8.0SQ 63 30 50 50
RAS-5FSXNH(E)
3N~ 400V/50Hz
13.0 MLFC 2.0SQ 40 30 20 20
RAS-6FSXNH(E) 13.0 MLFC 2.0SQ 40 30 20 20
RAS-8FSXNH(E) 15.0 MLFC 2.0SQ 40 30 20 20
RAS-10FSXNH(E) 18.7 MLFC 3.5SQ 40 30 30 30
RAS-12FSXNH(E) 20.0 MLFC 3.5SQ 40 30 30 30
ELB: Earthleakage Breaker (eld-supplied), CB: Circuit Breaker (eld-supplied), MLFC: Flame Retardant Polyex Wire
Install main switch and ELB for each system separately. Select the high response type of ELB that acts within 0.1 second.
60
PMML0294A rev.2 - 07/2014
Electrical wiring
PMML0294A_rev.2_02-2014.indb 60 14/07/2014 12:28:34

Other manuals for Hitachi RPC-6.0FSN3E