3  Unit number setting (RSW2 & DSW6). The indoor unit 
number of all indoor units are not required. The indoor unit 
numbers are set by the auto-address function. If the indoor 
unit number setting is required, set the unit number of all 
indoor units respectively and serially by following setting 
position. It is recommended that the unit number setting start 
from “1”. For the centralized control, this setting is required.
Factory setting
DSW6 (Tens digit) RSW2 (Units digit)
1 2 3 4 5 6
ON
0
9
8
7
6
5
4
3
2
1
? NOTE
•  For  units  supporting  H-LINK  II:  the  unit  numbers  can  be  set  for 
maximum 64 indoor units (Number 0-63).
•  For  units  supporting  H-LINK:  the  units  numbers  can  be  set  for 
maximum 16 indoor units (Number 0-15).
Example: set at number 16 unit
DSW6 (Tens digit) RSW2 (Units digit)
1 2 3 4 5 6
ON
0
9
8
7
6
5
4
3
2
1
4  Capacity code setting (DSW3). No setting is required, due to 
setting before shipment. This switch is used for setting the 
capacity code which corresponds to the Horse Power of the 
indoor unit.
Horsepower 1.5 2.0 2.5 3.0
Setting 
position
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
Horsepower 4.0 5.0 6.0
Setting 
position
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
5  Unit Model Code Setting (DSW4). No setting is required. It is 
for setting the model code of the indoor unit.
Factory setting
6  Refrigerant cycle number setting (RSW1 & DSW5). Setting is 
required. Setting positions before shipment are all OFF.
Factory setting
DSW5 (Tens digit) RSW1 (Units digit)
1 2 3 4 5 6
ON
0
9
8
7
6
5
4
3
2
1
? NOTE
•  For units supporting H-LINK II: the refrigerant cycle numbers can be 
set for maximum 64 cycles (Number 0-63).
•  For units supporting H-LINK: the refrigerant cycle numbers can be set 
for maximum 16 cycles (Number 0-15).
Example: set at number 5 cycle
DSW5 (Tens digit) RSW1 (Units digit)
1 2 3 4 5 6
ON
0
9
8
7
6
5
4
3
2
1
7  Fuse recover (DSW7). In the case of applying high voltage 
to the terminal 1 and 2 of TB2, the fuse (0.5A) on the PCB 
is cut, rstly reconnect the wirings correctly to TB2, and then 
turn on Number 1 pin.
Factory setting High voltage
ON
ON
8  Optional function setting (DSW9). No setting is required. 
Factory setting
? NOTE
•  The “■” mark indicates position of dip switches. Figures show setting 
before shipment.
•  When the unit number and the refrigerant cycle are set, record the unit 
number and refrigerant cycle to facilitate maintenance and servicing 
activities thereafter.
ELECTRICAL WIRING
PMML0551 rev.4 - 07/2023 - A10762310A
29
EN