UNITS INSTALLATION
PMML0385 rev.2 - 12/2018
8
RPI-(2.0-3.0)FSN5E
RPI-(4.0-6.0)FSN5E
 
Mounting the suspension bolts
 - Using the dimension shown above select the nal 
location and installation direction of the Indoor Unit 
paying careful attention to the space for the piping, wiring 
and maintenance.
 - Install the sling bolts, M10 or greater are also 
recommended, and suspend the indoor unit using the 
following steps:
1  Hook suspension bracket to the nut and washer of each sling 
bolt, as shown, starting from one side.
2  After checking the nut and washer are correctly xed by the 
retainers of the suspension bracket, hook the suspension 
bracket of the other side to nut and washer.
Left side
Suspension 
bolt
Suspension 
bracket
Inlet air
Washer
Nut
Right side
Washer
Nut
 
Drain pan level
FRONT VIEW
Condensate drain connection
 - Make sure that the foundation is at, taking into account 
the maximum foundation gradient.
 - The unit should be installed so that one side of the unit 
is slightly (approximately 5mm) lower than the other 
side, in order to avoid the incorrect position of the drain 
discharge.
Tighten the nuts of the suspension bolts with the suspension 
brackets after adjustment is completed. Special plastic paint 
must be applied to the bolts and nuts in order to prevent them 
from loosening.
? NOTE
Keep the unit as well as relevant equipment covered with the vinyl cover 
during installation work.