TROUBLESHOOTING
17. TROUBLESHOOTING
17.1. ALARM CODES
If RUN lamp flashes for 2 seconds, there is a failure in
transmission between Indoor Unit and Remote Control
Switch. Possible causes are:
Remote Cable broken
Contact Failure in Remote Control Cable
IC or Microcomputer defective
In any case, ask your service contractor
-
-
-
-
In RUN lamp flashes 6 times (5 seconds) with unit number
and alarm code displayed:
NOTE:
The alarm code displayed (see table below) and ask your
service contractor
-
Alarm Codes
Code Category Contents of Abnormality Leading Cause

Indoor unit Safety Device of the Indoor Unit is tripped Failure of Fan Motor, Float Switch PCB, Relay

Outdoor Unit Safety device of outdoor unit is tripped High pressure Switch, failure of fan Motor

Transmission
Abnormality between Indoor and Outdoor Unit (or Indoor)
Incorrect wiring, failure of PCB, tripping of Fuse.
Power supply off.

Abnormality of Power source wiring Reverse phase incorrect wiring

Cycle Abnormality high temperature in the top of comp.
Insufficient Refrigerant. Ref-leakage, clogging
capillary

Sensor in Indoor Unit
Inlet Air Thermistor
Failure of Thermistor, sensor, connection

Outlet Air Thermistor

Freeze protection Thermistor

Tripping of Protection Device for Fan Motor
Failure of Fan Motor

Sensor on Outdoor Unit
Top Compressor Thermistor
Failure of Thermistor, sensor, Connection

Outdoor Air Thermistor

Evaporating thermistor (defrosting)

System
Incorrect Setting of Outdoor and Indoor Unit Incorrect Setting of Capacity Code.

Incorrect Setting in Indoor/Outdoor Unit No.
Existence of the same Indoor Unit No. in the same
refrigerant cycle

Abnormality of Protective Circuit in Outdoor Unit
Failure of Indoor Unit PCB. Incorrect Wiring
Connection to PCB in Outdoor Unit.

Abnormality of Running Current at Compressor
Overcurrent, Melted Fuse or failure of current
sensor.

Pressure
Excessive Overload during Cooling Operation
Heat Exchanger Airflow obstacle, short circuit and
locked fan motor.

Excessive Overload during Heating Operation Heat Exchanger Airflow obstacle, short circuit.

Low pressure Decrease Protection Activating Insuficient refrigerant. Refrigerant Leak (Hex Lock)