2
Working Range
2. Working Range
Power Supply
Working Voltage: 90% to 110% of the Rated Voltage
Voltage Imbalance: Within a 3% Deviation from Each Voltage at the Main Terminal of Outdoor Unit
Starting Voltage: Higher than 85% of the Rated Voltage
Temperature Range
The temperature ranges are given in the following table Operate within this range.
°C
Maximum Minimum
Cooling Operation
Indoor 32 DB/23 WB 21 DB/15 WB
Outdoor 43 DB * -5 DB *
Heating Operation
Indoor 27 DB 15 DB
Outdoor 23 DB/17WB * -20 DB/-21 WB *
DB: Dry Bulb, WB: Wet Bulb
*: The temperature may change depending on the outdoor units.