7.2 Details for Motion Sensor Control
The motion sensor control adjusts automatically
the following items depending on a situation.
* Setting Temperature:
The temperature is adjusted 1
o
C or 2
o
C for
saving capacity.
* Air Flow Volume:
The air flow volume is adjusted to lower one
volume or to “Slo” (except during the dry
operation).
* Air Flow Direction:
The air flow direction is adjusted to horizontal.
7.3 Descriptions for Setting Items
l
Motion Sensor Setting
* ON: The operating control function by the
motion sensor is activated.
* OFF: The operating control function by the
motion sensor is not activated.
(The default setting is “ON”.)
2
If absent
“If absent” is set for the indoor unit operation
after the motion sensor detects as absence for
set time in “Check interval”. The operation can
be selected from “Running”, “Stand-by” or “Stop”
on the remote control switch.
(The default setting is “Running”.)
* Running:
The operation is continued with saving the
capacity after detected as an absence.
If the human activity is detected for a period of
time, the normal operation will be performed
again.
* Stand-by:
The operation mode is the fan operation at “Slo”
speed. If the human activity is detected for
a period of time, the normal operation will be
performed again.
* Stop:
The operation is stopped by the remote control
switch when all the indoor units with motion
sensor detect absence which are connected
with same remote control switch.
If the human activity is detected for a period of
time by the stoppage, the normal operation is
performed again.
3
Check Interval
When the motion sensor detects an absence
at selected check interval time, the function “If
absent” will be executed. The interval can be
selected from 30, 60, 90 120 or 180 minutes.
(The default setting is 30 minutes.)
(1) Press “ ” (menu).
Select “Motion Sensor Setting” from the
menu by pressing “ ” or “ ” and press “OK”.
Menu
Motion Sensor Setting
Total Heat Exchanger SET
VENTI
Louver Open/Close 02
/
15:10(Fri)
Louver Setting
03
ENT
. RTN.SEL.
OK
OK
OK
(2) “Motion Sensor Setting” is displayed.
The highlighted item is shifted to “Sensor”, “If
absent” and “Check interval” by pressing “ ”
or “ ”.
Motion Sensor Setting
Sensor
ON
If absent
Running
Check interval
30MIN
ENT
. RTN.SEL. ADJ
OK
OK
(3) Press “ ” or “ ” and select “Sensor”.
Motion Sensor Setting
Sensor
ON
If absent
Running
Check interval
30MIN
ENT
. RTN.SEL. ADJ
OK
OK
(4) The display is switched “ON” and “OFF” in
order by pressing “ ” or “ ” and change the
setting.
If other settings are not required, move to
procedure (9).
Motion Sensor Setting
Sensor
ON
If absent
Running
Check interval
30MIN
ENT
. RTN.SEL. ADJ
OK
OK
7.4 Setting of Motion Sensor
• To set “Sensor”, move to procedure (3).
• To set “If absent”, move to procedure (5).
• To set “Check interval”, move to procedure (7).