Wire Connection and Optional Devices
7.5.5 Applicable Breakers
200V class
・When inverter ND rating setting
- When inverter LD/VLD rating setting
* If export to the U.S. or Canada or compliance with UL/cUL
standards is required, you need to use wires and breakers
specified in the UL/cUL standards. For details, see "1.7
Compliance with UL Standards".
* The models described in the table are examples of selection.
When using the device, choose a model that has appropriate
breaking capacity and sensitive current by taking short circuit
current and relevant laws and regulations into consideration
based on the rated current shown in the table.
* The applicable motor capacity is a selection example when
Hitachi IE3 4-pole motor model 60HZ 200VAC (200V class) is
used.
* For the power line diameter, see the "Power line" column in the
table shown in "7.5.4 Recommended Wire Diameter, Wiring
Tools, and Crimping Terminals".
* The electric durability ensured when the magnetic contactor is
used in AC-1 class is 500,000 times, while emergency stop
during motor operation is 25 times.
* If there is emergency stop during motor drive or commercial
operation is performed, choose the magnetic contactor on the
motor side in AC-3 class against the rated current of motor.
* If the rated capacity of inverter is larger than the motor capacity,
choose instruments based on the inverter model.
P1 model
P1-*******
(P1-****)
motor
(kW)
Applicable instrument (input voltage 200-220V)
Without power factor improvement reactor (DCL or ACL)
With power factor improvement reactor (DCL or ACL)
Earth-leakage breaker (ELB)
Example of
model
Rated current
AC-1 AC-3
Example of
model
Rated current
AC-1 AC-3
P1-00044-L(P1-004L)
0.4 EB-30E 5 HS8 HS8 EB-30E 5 HS8 HS8
P1-00080-L(P1-007L)
0.75 EB-30E 10 HS8 HS8 EB-30E 5 HS8 HS8
P1-00104-L(P1-015L)
1.5 EB-30E 15 HS8 HS8 EB-30E 10 HS8 HS8
P1-00156-L(P1-022L)
2.2 EB-30E 20 HS8 HS8 EB-30E 15 HS8 HS8
P1-00228-L(P1-037L)
3.7 EB-30E 30 HS8 HS20 EB-30E 20 HS8 HS20
P1-00330-L(P1-055L)
5.5 EB-50E 40 HS20 HS25 EB-30E 30 HS8 HS20
P1-00460-L(P1-075L)
7.5 EB-50E 50 HS35 HS35 EB-50E 40 HS20 HS25
P1-00600-L(P1-110L)
60 HS35 HS50
P1-00800-L(P1-150L)
100 HS50 H65C
P1-00930-L(P1-185L)
100 HS50 H65C
P1-01240-L(P1-220L)
22 EXK225 150 H80C H125C RXK125-S
125 H65C H80C
P1-01530-L(P1-300L)
30 EXK225 200 H125C H150C EXK225
150 H80C H125C
P1-01850-L(P1-370L)
200 H100C H125C
P1-02290-L(P1-450L)
45 EX400 300 H200C H250C EXK225
225 H125C H150C
P1-02950-L(P1-550L)
55 EX400 400 H200C H300C EX400 300 H150C H250C
P1 model
P1-*******
(P1-****)
motor
(kW)
Applicable instrument (input voltage 200-220V)
Without power factor improvement reactor (DCL or ACL)
With power factor improvement reactor (DCL or ACL)
Earth-leakage breaker (ELB)
Earth-leakage breaker (ELB) Magnetic contactor (MC)
Example of
model
Rated current
AC-1 AC-3
Example of
model
Rated
current
AC-1
AC-3
P1-00044-L(P1-004L)
0.75 EB-30E 10 HS8 HS8 EB-30E 5 HS8 HS8
P1-00080-L(P1-007L)
1.5 EB-30E 15 HS8 HS8 EB-30E 10 HS8 HS8
P1-00104-L(P1-015L)
2.2 EB-30E 20 HS8 HS8 EB-30E 15 HS8 HS8
P1-00156-L(P1-022L)
3.7 EB-30E 30 HS8 HS20 EB-30E 20 HS8 HS20
P1-00228-L(P1-037L)
5.5 EB-50E 40 HS20 HS25 EB-30E 30 HS8 HS20
P1-00330-L(P1-055L)
7.5 EB-50E 50 HS35 HS35 EB-50E 40 HS20 HS25
P1-00460-L(P1-075L)
60 HS35 HS50
P1-00600-L(P1-110L)
100 HS50 H65C
P1-00800-L(P1-150L)
100 HS50 H65C
P1-00930-L(P1-185L)
22 EXK225 150 H80C H125C RXK125-S
125 H65C H80C
P1-01240-L(P1-220L)
30 EXK225 200 H125C H150C EXK225 150 H80C H125C
P1-01530-L(P1-300L)
250 H150C H200C EXK225 200 H100C H125C
P1-01850-L(P1-370L)
45 EX400 300 H200C H250C EXK225 225 H125C H150C
P1-02290-L(P1-450L)
55 EX400 400 H200C H300C EX400 300 H150C H250C
P1-02950-L(P1-550L)
75 EX600B 500 H300C H400C EX400 400 H200C H300C