7-17
Chapter 7
Wire Connection and Optional Devices
7.5.7 Wiring to Power Supply and Motor
We want to connect a power supply to the inverter.
We want to connect a motor to the inverter.
Connect R, S, T (L1, L2, L4) to the AC power
supply.
Connect U, V, W (T1, T2, T3) to the motor.
The common wiring examples are shown below.
Use the input power supply within the
range shown below.
Voltage
class
Input range
200V class 200-240VAC (allowable variation
range: +10%/-15%)
Power supply frequency: 50Hz/60Hz
(variation range: ±5%)
400V class 380-500VAC (allowable variation
range: +10%/-15%)
Power supply frequency: 50Hz/60Hz
(variation range: ±5%)
Driving a 200V motor using a 400V-class
inverter may burn the motor.
Q
A
DANGER
Do
ELB
Earth
-
leakage
breaker
Magnetic
contactor
MC
3-phase
AC
power
supply
R/L1
S/L2
T/L3
R0
T0
U/T1
V/T2
W/T3
Control circuit
power supply
D-class grounding
(200V class)
C-class grounding
(400V class)
J51 connector
3-phase AC motor
M
Main circuit
terminal area
3
Short bar or terminal
Short bar
Enable
P
PD
RB
N
Short bar
Internal EMC filter