? NOTE
Placeinsulation(eldsupplied)toprotectcablesandpipesfrom
beingdamagedbyplateedges.
b. For the downward piping
Gas piping
Knock-out hole
Bottom base
Cables
Liquid piping
? NOTE
Cablesshallnotcontactdirectlytothepipes.
c. For the rear side piping
Rear Cover
? NOTE
Removetherear pipe cover under the rear cover and remove
partfollowingtheslit.
2 Mount the piping cover in order to avoid water entering into
the unit. Seal the holes where pipes and wires are inserted,
3
directly, it is recommended use a tube bender.
4 Check to ensure that the stop valves are closed completely
before connecting pipes.
5
pipe before tightening.
6 After connecting the refrigerant piping, seal the open space
between knockout hole and refrigerant pipes by using
insulation material.
7 Operation of stop valve should be performed according to
Outdoor unit stop valve
Spindle Type
Spindle valve
Flare nut
Cap
Check joint for service port
Closed upon factory shipping
Tightening Torque (Nm)
Liquid valve 7-9 33-42 33-42
14-18
Gas valve 9-11 68-82 50-62
Spindle Type
Nº Description Remarks
Cap
Allen wrench
Gas valve: Hex 5 mm
Refrigerant Piping Field Supplied
Flare nut
Refrigerant Pressure To Outdoor Unit
Seat Surface Fully closed position
Check Joint
Only the charging hose can be
connected
Charge port cap
O-Ring Rubber
Spindle valve
Open – Counterclockwise
Close – Clockwise
Do not apply two
spanners at this
position. If applied,
leakage will occur.
Stop valve
(Spindle type)
Flare nut
Refrigerant piping & refrigerant charge
PMML0545 rev.2 - 04/2021
10