Use two spanners here 
for pipe connection
Do not work with two 
spanners here. 
Refrigerant leakage 
shall occur
! CAUTION
• Atthetestrun,fullyopenthespindleandballstopvalve.
• Ifnotfullyopened,thedeviceswillbedamaged.
• Donotattempttoturnservicevalverodbeyonditsstop.
• Donotloosenthestopring.Ifthestopringisloosened,itisdangerous
sincethespindlewillhopout.
• Anexcessorashortageofrefrigerantisthemaincauseoftrouble
totheunits.Chargethecorrectrefrigerantquantityaccordingtothe
descriptionoflabelattheinsideofservicecover.
• Checkforrefrigerantleakageindetail.Ifalargerefrigerantleakage
occurs,itwillcausedifcultywithbreathingorharmfulgaseswould
occurifarewasbeingusedintheroom.
8.3  BRAZING WORK
! CAUTION
• Usenitrogengasforblowingduringpipebrazing.Ifoxygen,acetylene
oruorocarbongasisused,itwillcauseanexplosionorpoisonous
gas.
• A lot of oxidation lm will occur inside of tubes if no nitrogen gas
blowingis performed duringbrazingwork. This lmwillbeecked
offafteroperationandwillcirculateinthecycle,resultinginclogged
expansionvalves,etc.Thiswillcausebadinuencetothecompressor.
• Useareducervalvewhennitrogengasblowingisperformedduring
brazing. The gas pressure should be maintained within 0.03 to
0.05MPa.Ifaexcessivelyhighpressureisappliedtoapipe,itwill
causeanexplosion.
8.4  REFRIGERANT CHARGE
! CAUTION
• Do not charge OXYGEN, ACETYLENE, or other ammable and
poisonousgasesintotherefrigerantbecauseanexplosioncanoccur.
Itis recommendedthatoxygenfree nitrogen bechargedfor these
typesoftestscyclewhenperformingaleakagetestoranairtighttest.
Thesetypesofgasesareextremelydangerous.
• Insulate the unions and are-nuts at the piping connection part
completely.
• Insulate the liquid piping completely to avoid a decrease of
performance;ifnot,itwillcausesweatingonthesurfaceofthepipe.
• Charge refrigerant correctly. Overcharging or insufcient charging
couldcauseacompressorfailure.
• Checkforrefrigerantleakageindetail.Ifalargerefrigerantleakage
occurred, it would cause difcultywith breathing or harmful gases
wouldoccurifarewerebeingusedintheroom.
• Ifthearenutistightenedtoohard,thearenutmaycrackaftera
longtimeandcauserefrigerantleakage.
8.5  CAUTION OF THE PRESSURE BY CHECK JOINT
When the pressure is measured, use the check joint of gas stop 
below.
At that time, connect the pressure gauge according to the 
following table because of high pressure side and low pressure 
side changes by operation mode.
Cooling 
operation
Heating 
operation
Check joint for gas stop valve “A” Low pressure High pressure
Check joint for piping “B” High pressure Low pressure
Check joint for liquid stop valve “C”
Exclusive for vacuum pump and 
refrigerant charge
? NOTE
Becarefulthatrefrigerantandoildonotsplashtotheelectricalpartsat
removingthechargehoses.
C
B
A
There may be gas 
trapped at the “O-ring 
screw” part, which may 
produce a sound when 
released upon removal 
of the cap. 
However, this is not a 
gas leakage.
Refrigerant piping & refrigerant charge
PMML0545 rev.2 - 04/2021
11
EN