Auto Heat / Cool
REF Access Description
Default 
Value
Range Steps Units Application
Notes
Auto Heat / Cool S SC S80 M
AHC Status Disable Disabled /Enabled 1 - ○ ○ - ○ (*1)
Hoff
Switch to Heat T 22 10~23 1 ºC ○ ○ - ○ (*2)
Coff Switch to Cool T 25 24~35 1 ºC ○ ○ - ○ (*2)
? NOTE
•  (*1): If Status (AHC)(“Status”)= “Disabled”, the operation mode is automatically set to “Heat”.
•  (*2): If Status (AHC)(“Status”)= “Enabled”
 
DHW
Available if Status (DHWs)= “Enabled”. 
REF Access Description
Default 
Value
Range Steps Units Application
Notes
DHW S SC S80 M
AutoST Circuit pump Disabled
Disabled, 
Enabled, 
Anti-Legionella
- - ○ ○ ○ ○ -
AutoT DHW Boost Push
Disabled, 
Push, 
Open, 
Closed
- - ○ ○ ○ ○ -
AutoDiff Boost setting  50 30 ~ (TDHWmax) - - ○ ○ ○ ○ (*1)
? NOTE
(*1): If DHW Boost (AutoT) is not set as “Disabled”.
8.6.2.11  I/O and Sensor 
Available if Controller type (LCDM)= “Unit” or “Unit+Room”
•  Inputs 
•  Outputs 
•  Auxiliary Sensors 
 
Inputs
REF Access Description Default Value Range Steps Units Application
Notes
Inputs S SC S80 M
I1 Input 1  Demand ON/OFF
*See “Inputs range 
visualization and 
constraints table” below
- - ○ ○ ○ ○ -
I2 Input 2  Eco C1 (if C1) - - ○ ○ ○ ○ -
I3 Input 3  SWP (if SWP) - - ○ ○ ○ ○ -
I4 Input 4  Solar (if Solar) - - ○ ○ ○ ○ -
I5 Input 5 Smart function (if Enabled) - - ○ ○ ○ ○ -
I6 Input 6 DHW Boost (if DHW) - - ○ ○ ○ ○ -
I7 Input 7 Power Meter 1 (If Enabled) - - ○ ○ ○ ○ -