9  TROUBLESHOOTING
Alarm code indication on remote control switch:
Alarm indication
Alarm code
 
Alarms for Indoor units:
Alarm     
Code
Retry 
Stop 
Code
Yutaki 
S/SC
Yutaki 
S80
Yutaki 
M
Origin Detail of Abnormality Main Factors
3 - o o o Communication
Transmission Alarm (Not outdoor 
unit detected)
Loose, disconnected, broken or 
short-circuited connector
11 - o o o Indoor
Water inlet thermistor abnormally 
(THMwi)
Loose, disconnected, broken or 
short-circuited connector
12 - o o o Indoor
Water outlet thermistor abnormally 
(THMwo)
Loose, disconnected, broken or 
short-circuited connector
13 – o o o Indoor
Indoor Liquid Pipe Temp Thermistor 
Abnormality (THMl)
Loose, disconnected, broken or 
short-circuited connector
14 – o o o Indoor
Indoor Gas Pipe Temperature 
Thermistor Abnormality (THMg)
Loose, disconnected, broken or 
short-circuited connector
15 - (o) (o) (o) Indoor
Water Circuit 2 thermistor 
abnormally (THMwo2)
Loose, disconnected, broken or 
short-circuited connector
16 - (o) (o) (o) Indoor
Water DHW thermistor abnormally 
(THMdhwt)
Loose, disconnected, broken or 
short-circuited connector
17 - (o) (o) (o) Indoor
Auxiliary sensor 2  thermistor 
abnormally (THMaux2)
Loose, disconnected, broken or 
short-circuited connector
18 - (o) (o) (o) Indoor
Auxiliary sensor 1  thermistor 
abnormally (THMaux1) 
Loose, disconnected, broken or 
short-circuited connector
19 - o - - Indoor
Water Plate HEX pipe thermistor 
abnormally (THMwohp)
Loose, disconnected, broken or 
short-circuited connector
19 - o - Indoor
Suction R134a  pipe thermistor 
abnormally (THMs)
Loose, disconnected, broken or 
short-circuited connector
23 - o - Indoor
Discharge R134a  pipe thermistor 
abnormally (THMd)
Loose, disconnected, broken or 
short-circuited connector
25 - (o) (o) (o) Indoor
Auxiliary sensor 3  thermistor 
abnormally (THMaux3)  
Loose, disconnected, broken or 
short-circuited connector
40 - o o o Indoor Incorrect LCD setting
Current LCD conguration does not 
allow proper operation
63 - (o) (o) (o) Communication
Transmission error between 
Central and indoor communication
Indoor fuse meltdown, Indoor/
central connection wiring (breaking, 
wiring error, etc.)
70 P70 o o o Indoor
Hydraulic alarm ow & Water Pump 
malfunction
Water ow is not detected in the 
hydraulic cycle or Pump defective
83 P83 o o o Indoor Hydraulic alarm pressure
Water pressure is not detected in 
the hydraulic cycle
72 o - - Indoor Thermostat Heater Alarm
High temperature is detected in 
Electric Heater 
73 o o o Indoor
Mixing over-temperature limit 
protection for Mixed circuit.
Circuit 2 supply temperature > 
Target temperature + offset
74 P74 o o o Indoor
Unit over-temperature limit 
protection
Two > Tmax +5K
TROUBLESHOOTING