ENGLISH
Circuit 2
REF Access Description
Default
Value
Range Steps Units Application
Notes
Circuit 2 S SC S80 M
Rfacth1 Compen.Factor Heat 2 OFF / 1~5 1 - (*1)
Maxfacthp1 Max Compen.Factor Heat + 10 0-10 1 ºC (*1)
Maxfacthn1 Max Compen.Factor Heat - -10 -10-0 1 ºC (*1)
Rfactc1 Compen.Factor Cool OFF OFF / 1~5 1 - (*2)
Maxfactcp1 Max Compen.Factor Cool + 5 0-10 1 ºC (*2)
Maxfactcn1 Max Compen.Factor Cool - -5 -10-0 1 ºC (*2)
? NOTE
(*1): If Water calculation mode for circuit 2 heating (C2WC)=Not “Disabled”.
(*2): If Water calculation mode for circuit 2 cooling (CC2WC)=Not “Disabled”.
Room Temperature Demand OFF
Circuit 1 (*1)
Circuit 2 (*2)
? NOTE
(*1):If Water calculation mode for circuit 1 in Heating (Water calculation mode for circuit 1 heating (C1WC)) or in Cooling (Water calculation mode
for circuit 1 cooling (CC1WC)) is not “Disabled”.
(*2): If Water calculation mode for circuit 2 in Heating (Water calculation mode for circuit 2 heating (C2WC)) or in Cooling (Water calculation mode
for circuit 2 cooling (CC2WC)) is not “Disabled”.
Circuit 1
REF Access Description
Default
Value
Range Steps Units Application
Notes
Circuit 1 S SC S80 M
RoffhC1 Room Demand OFF Heat 3 OFF/1~5 1 ºC (*1)
RoffcC1 Room Demand OFF Cool 3 OFF/1~5 1 ºC (*2)
? NOTE
(*1): If Water calculation mode for circuit 1 heating (C1WC)=Not “Disabled”.
(*2): If Water calculation mode for circuit 1 cooling (CC1WC)=Not “Disabled”.
UNIT CONTROLLER
PMML0335A rev.1 - 04/2016
139