Copyright HK Instruments 2018 www.hkinstruments. Installaon version 6.0 2018
INSTALLATION
INSTRUCTIONS
DIFFERENTIAL PRESSURE TRANSMITTERS
DPT-R8 Series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
SPECIFICATIONS
ThankyouforchoosinganHKInstrumentsDPTseriesdierenal
pressuretransmier.TheDPTseriesisintendedforuseincommer-
cial environments. It is designed with six unit selecons (Pa, kPa,
mbar,inchWC,mmWC,psi)andeighteldselectablemeasurement
ranges (unidireconal and bi-direconal) to meet yourapplicaon
requirements. The DPT-R8 series is comprised of the DPT250-R8
with ranges from 25 Pa to 250 Pa, the DPT2500-R8 with ranges
from 100 Pa to 2500Pa, and the DPT7000-R8 with ranges from
1000Pato7000Pa.
All DPT-R8 series dierenal pressure transmiers are available
withdisplayandautozerocalibraon.
DPT-R8seriesdevicesarecommonlyusedinHVAC/Rsystemsfor:
•fan,blowerandltermonitoring
•pressureandowmonitoring
•valveanddampercontrol
•pressuremonitoringincleanrooms
SPECIFICATIONS
Performance
Accuracy (from applied pressure):
Models250and2500:
Pressure<125Pa=1%+±2Pa
Pressure>125Pa=1%+±1Pa
Model7000:
Pressure<125Pa=1.5%+±2Pa
Pressure>125Pa=1.5%+±1Pa
(including:generalaccuracy,linearity,hysteresis,long
termstability,andrepeonerror)
Thermal eects:
Temperaturecompensated0...50°C
Overpressure:
Proofpressure:25kPa
Burstpressure:30kPa
Zero point calibraon:
Automacautozeroormanualpushbuon
Response me:
8.0sor0.8s,selectableviajumper
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
Pa,kPa,mbar,inchWC,mmWC,psi,selectablevia
jumper
Measuring element:
MEMS,noow-through
Environment:
Operangtemperature:-20...50°C,
-40Cmodel:-40...50°C
AZ-model:-20...50°C,
Modelswithautozerocalibraon:-5...50°C
Storagetemperature:-40...70°C,
-40Cmodel:-40...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:90.0x95.0x36.0mm
Weight:
150g
Mounng:
2each4.3mmscrewholes,onesloed
Materials:
Case:ABS
Lid:PC
Ductconnectors:ABS
Tubing:PVC
Protecon standard:
IP54
Display (Oponal)
2-linedisplay(12characters/line)
Line1:acvemeasurement
Line2:units
Electrical connecons:
4-screwterminalblock
Wire:0.2–1.5mm
2
(12–24AWG)
Cableentry:M16
Pressure ngs:
Maleø5,0mmand6,3mm
+Highpressure
−Lowpressure
Electrical
Voltage:
Circuit:3-wire(VOut,24V,GND)
Input:24VACorVDC,±10%
Output:0–10V
Powerconsumpon:<1.0W,
-40Cmodel:<4.0Wwhen<0°C
Resistanceminimum:1kΩ
Current:
Circuit:3-wire(mAOut,24V,GND)
Input:24VACorVDC,±10%
Output:4–20mA
Powerconsumpon:<1.2W,
-40Cmodel:<4.2Wwhen<0°C
Maximumload:500Ω
Minimumload:20Ω
Conformance
MeetstherequirementsforCEmarking:
EMCDirecve2014/30/EU
RoHSDirecve2011/65/EU
WEEEDirecve2012/19/EU