PRODUCT DATA
68-0312-07
VisionPRO
®
8000 with RedLINK™
APPLICATION
The VisionPRO® 8000 with RedLINK™ features an
effortless, 7-Day programmable touchscreen thermostat
that provides control of temperature, humidification,
dehumidification, and ventilation for up to 4 Heat/2 Cool
heat pump systems or up to 3 Heat/2 Cool conventional
systems for residential and commercial applications.
FEATURES
RedLINK™ Compatible
Increase your content and profit per job by including
RedLINK™ accessories that meet your customers’
comfort and convenience needs. RedLINK accessories
include the Wireless Outdoor Sensor, Portable Comfort
Control (PCC), Equipment Interface Module (EIM),
RedLINK Internet Gateway, Wireless Indoor Sensor,
TrueZONE™ zoning panel with Wireless Adapter, Vent
Boost Remote and Entry/Exit Remote.
Also Compatible with Equipment Remote Module
(ERM) ERM5220R
Customizable Service Reminders
Set up to 10 service reminders. Choose from the pre-set
options or customize your own. Reminders can be
based on date or the outdoor temperature.
Sensor Inputs
Thermostat - S1
EIM - S1, S2, S3, S4
Assignable inputs allow you to setup Indoor and
Outdoor Temperature Sensors, Discharge and Return
Air Sensors or Dry Contact Devices. Dry Contact
Devices can be used to trip pre-set or customized alerts
on the thermostat home screen. Note: Dry Contact
Alerts require an Equipment Interface Module (EIM).
User Interaction Log
The interaction log stores history of thermostat setting
changes including temperature, system and installer
setup. You can use the interaction log to save time by
determining if the issue is a system error or an acciden-
tal user error. The Interaction Log is only viewable on a
computer after you download it from the thermostat to
a microSD card.
Selectable for Residential and Light Commercial
Applications
One thermostat does it all to meet the needs of Resi-
dential and Light Commercial applications. Simply
select Residential or Commercial during the installer
setup. If Commercial is selected, the thermostat will use
commercial language, meet building codes and offer
365 day holiday scheduling.
MicroSD Card Port for Quick Installer Setup
Save time by using a microSD card to upload installer
settings and service reminders in one simple step.
Selectable Sensors
When paired with a Wireless Indoor Sensor(s) you have
the ability to choose which sensor(s) to use for tem-
perature, humidification and dehumidification. They
can be used in combination for temperature averag-
ing—or individually—to condition humidity levels in
separate spaces.
pm
HOME
COOL
OFF
I
N
TE
R
N
E
T
POWER
R
E
D
LI
N
K

Table of Contents

Other manuals for Honeywell Home TH8110R1008

Question and Answer IconNeed help?

Do you have a question about the Honeywell Home TH8110R1008 and is the answer not in the manual?

Honeywell Home TH8110R1008 Specifications

General IconGeneral
CompatibilityHeating and Cooling systems
Wi-Fi ConnectivityNo
Programmability7-Day programmable
BacklightYes
Hold FunctionYes
Battery BackupYes
Voltage24VAC

Summary

VisionPRO® 8000 with RedLINK™ Product Introduction

Application and Key Features Overview

Describes the thermostat's application and lists its main features, including RedLINK compatibility and sensor options.

Product Specifications

Thermostat and System Performance Specifications

Details electrical ratings, RedLINK communication, temperature ranges, sensor accuracy, and mounting.

Operation Indicators and Mounting

Explains system status indications and physical mounting requirements for the thermostat.

System Installation Guide

Installation Guidelines and Preparation

Covers essential guidelines, password retrieval, and initial wiring steps for thermostat installation.

Finding Thermostat Password (Date Code)

Details how to locate the thermostat password required for installer options and setup.

Installation Options and Model Information

System Wiring and Model Comparison

Explains wiring options and compares VisionPRO® 8000 models based on stages and features.

RedLINK Device Installation Procedures

RedLINK Installation Guidelines and EIM Setup

Provides installation guidelines for RedLINK devices and steps for installing the Equipment Interface Module (EIM).

Wiring Common and Sensor Connections

Details wiring the 24 Vac common and connecting discharge/return air sensors.

Sensor Mounting Location Guidelines

Discharge and Return Air Sensor Placement

Guides on selecting proper mounting locations for discharge and return air temperature sensors in ductwork.

Thermostat Installation Location Selection

Choosing an Optimal Thermostat Location

Provides guidance on choosing an optimal location for thermostat installation to ensure accurate readings.

Thermostat Installation and Wiring

Wallplate and Power Connection

Step-by-step instructions for installing the wallplate, connecting power via batteries or C-wire.

Thermostat Direct Wiring

Provides wiring instructions for connecting the thermostat directly to heating/cooling equipment.

Optional RedLINK™ Accessories and Initial Setup

Optional Accessory Battery Installation

Instructions for installing batteries in optional accessories like outdoor sensors and portable comfort controls.

Performing Initial Setup Procedures

Outlines the steps for performing the initial setup, including system type and accessory configuration.

RedLINK Device Linking and Setup Completion

Linking Thermostat to EIM or Wireless Adapter

Guides the process of connecting the thermostat to the EIM or wireless adapter, confirming the link.

Linking RedLINK Accessories to Thermostat

Explains how to connect RedLINK accessories to the thermostat by pressing the connect button.

Setup Completion and Accessory Addition

Completing the Initial Setup Process

Details finishing the setup process by selecting desired options and confirming completion on the thermostat.

Adding RedLINK Accessories Post-Setup

Provides steps to add RedLINK accessories after the initial thermostat setup is complete, via Wireless Manager.

RedLINK Accessory Connection Details

Locating Connect Buttons on Accessories

Identifies the location of the connect buttons on various RedLINK accessories for the linking process.

Troubleshooting Common Errors and Connections

Interpreting Error Messages

Lists and explains error codes that may appear during operation or setup, guiding troubleshooting steps.

Connecting RedLINK Gateway and TrueSTEAM

Details connecting the RedLINK Internet Gateway and TrueSTEAM wireless adapter for proper operation.

Wireless Sensor and Remote Setup Procedures

Wireless Indoor Sensor and Remote Installation

Instructions for installing batteries and connecting wireless indoor sensors and remotes for control.

Accessing Installer Options and Settings

Finding Thermostat Password (Date Code)

Details how to locate the thermostat password required for installer options and setup.

Installer Options Menu Navigation

Lists available options within the Installer Options menu, such as Installer Setup and Wireless Manager.

Installer Setup Configuration Process

Making Installer Setup Changes

Guides on using a microSD card to save setup time and make changes to installer setup options.

Understanding Installer Setup (ISU) Table

Introduces the Installer Setup table, detailing ISU numbers, names, settings, and defaults for configuration.

Installer Setup - Heating System Configuration

Heating System and Equipment Setup

Details ISUs for heating system type, equipment, and radiant stage settings for proper configuration.

Stage Control Settings Explained

Covers settings for radiant stage 1 and 2, defining their availability and wiring requirements.

Installer Setup - Cooling and Heat Stages

Cool Stages and Compressor Configuration

Details ISUs for configuring cool stages, compressor stages, and heat stages/backup heat stages.

Cool Stage 3 & 4 and Heat Stage Configuration

Explains configuration for Cool Stage 3/4 and Heat Stage, including terminal requirements and availability.

Installer Setup - Advanced Heating and Backup Heat

Cool Stage 4 and Backup Heat Settings

Covers ISUs for Cool Stage 4, backup heat type, backup heat stages, and fan control in heat mode.

Economizer Fault and Wiring Configuration

Configures economizer fault detection and wiring options for economizer control with or without an EIM.

Installer Setup - Backup Heat and Economizer Details

Backup Heat Operation and Type Settings

Covers ISUs for running backup heat, backup heat type, and economizer fault/wiring settings.

Economizer Fault and Wiring Options

Explains economizer fault detection and wiring options for economizer control with or without an EIM.

Installer Setup - A-L/A Terminal and System Changeover

A-L/A Terminal Functions and Usage

Details the functions of the A-L/A terminal for Time of Day, Economizer, and Heat Pump Fault alerts.

System Changeover Mode Configuration

Configures system changeover between manual and automatic modes for heating and cooling control.

Installer Setup - Changeover and Control Options

Auto Changeover Deadband Setup

Sets the deadband for auto changeover, defining the separation between heat and cool setpoints.

Control Options for Temperature Regulation

Allows selection of Basic or Advanced control options for temperature regulation and stage control.

Installer Setup - Cooling Differential Settings

Cool Differential Settings by Stage

Configures differential settings for cool stages 2, 3, and 4 to manage temperature control and stage activation.

Radiant Heat Differential Stage 2 Configuration

Sets the differential for radiant heat stage 2, impacting heating control based on temperature drops.

Installer Setup - Heating Differential Settings

Heat Differential Settings by Stage

Configures differential settings for heat stages 2 and 3, influencing heating stage activation based on temperature.

Compressor Heat Differential Stage 1 Setup

Sets the differential for compressor heat stage 1, affecting geothermal radiant heat control.

Installer Setup - Backup Heat and Timer Configuration

Compressor Heat Differential Stage 2 Setup

Sets the differential for compressor heat stage 2, affecting heat pump and geothermal radiant heat control.

Backup Heat Droop and Upstage Timer Settings

Configures backup heat droop for stages 1 and 2, and the upstage timer for backup heat activation.

Installer Setup - Cycle Rates and Lockout Settings

Heat and Radiant Cycle Rate Configuration

Sets cycle rates per hour for heat stages and radiant stages to manage system cycling and efficiency.

Outdoor Temperature Lockouts for Ventilation

Configures lockout setpoints based on outdoor temperature for heat pump and backup heat operation.

Installer Setup - Cooling Cycle Rate Configuration

Cool/Compressor Cycle Rates by Stage

Sets cooling cycle rates per hour for stages 1 through 4, impacting compressor cycling and efficiency.

Installer Setup - Heat Cycle Rate Configuration

Heat Cycle Rates by Stage

Configures heat cycle rates per hour for stages 1 through 3, defining system cycling for various heating types.

Installer Setup - Backup Heat Cycle Rate Configuration

Backup Heat Cycle Rates by Stage

Sets backup heat cycle rates per hour for stages 1 and 2, impacting backup heating system cycling.

Installer Setup - Fan, Purge, and Schedule Settings

Compressor Off Time and Extended Fan Run

Configures compressor minimum off time and extended fan run time for cooling and heating efficiency.

Scheduled Periods and Pre-Occupancy Purge

Sets scheduled periods per day and configures pre-occupancy purge for commercial comfort.

Installer Setup - Override and Recovery Settings

Override Type and Duration Configuration

Configures standard or occupancy-initiated overrides and sets the duration for temporary schedule changes.

Heat Recovery Ramp Rate Configuration

Sets minimum and maximum heat recovery ramp rates and associated outdoor temperatures for efficient heating.

Installer Setup - Heat Recovery Outdoor Temperature Settings

Minimum/Maximum Heat Recovery Outdoor Temperature

Sets outdoor temperature thresholds for minimum and maximum heat recovery ramp rates, optimizing energy use.

Installer Setup - Cool Recovery Ramp Rate Settings

Minimum Cool Recovery Ramp Rate Configuration

Configures the minimum cool recovery ramp rate and associated outdoor temperature for efficient cooling.

Maximum Cool Recovery Ramp Rate and Outdoor Temperature

Sets the maximum cool recovery ramp rate and associated outdoor temperature for efficient cooling.

Installer Setup - Maximum Cool Recovery Ramp Rate

Maximum Cool Recovery Ramp Rate Configuration

Sets the maximum cool recovery ramp rate and associated outdoor temperature for efficient cooling.

Installer Setup - Adaptive Recovery and Lockout Settings

Adaptive Recovery and Keypad Lockout Configuration

Configures adaptive recovery for efficient heating/cooling and keypad lockout for security.

Setpoint Limits and Remote Control Configuration

Sets minimum cool and maximum heat setpoints, and configures remote entry/exit remote settings.

Installer Setup - Remote Sensors and Control

Remote Entry/Exit Remote Setpoints

Configures setpoints for residential and commercial entry/exit remotes for various modes like Home, Away, Vacation.

Wired Sensor Configuration Options

Covers configuration for wired sensors like indoor, outdoor, return, and discharge sensors.

Installer Setup - Sensor Configuration Details

Indoor and Outdoor Sensor Setup

Configures indoor and outdoor sensors, including naming, type (10K/20K), and temperature control usage.

Return and Discharge Sensor Configuration

Configures return and discharge sensors, including type (10K/20K) and connection terminals.

Installer Setup - Dry Contact Alerts Configuration

Dry Contact Device and Alert Setup

Details connecting dry contact devices to S terminals for alerts like drain pan, filter, water leak, and shutdown.

Custom Alert Name and Message Setup

Allows setting custom alerts for dry contact devices, specifying names and messages for notifications.

Installer Setup - Remote Setback and Economizer Settings

Remote Setback Configuration

Sets up remote setback using occupancy sensors, including terminal connections and open/closed contact options.

Economizer Fault and Wiring Configuration

Configures economizer fault detection and wiring options for economizer control with or without an EIM.

Installer Setup - Alert Configuration for System Events

Drain Pan and Dirty Filter Alert Setup

Configures alerts for drain pan status and dirty filters, including contact type and terminal connections.

Water Leak and System Shutdown Alert Setup

Sets up alerts for water leaks and system shutdowns, specifying contact type and terminal connections.

Installer Setup - Service, Fan, and Custom Alerts

Service Needed and Fan Failure Alert Setup

Configures alerts for service needed and fan failure, specifying contact type and terminal connections.

Custom Alert and Filter Reminder Setup

Allows setup of custom alerts and filter reminders for system maintenance and performance.

Installer Setup - Custom Alerts and Filter Reminders

Custom Alert Naming and Messaging

Enables setting custom alert names and messages for dry contact device notifications.

Filter Type and Number of Filters Configuration

Configures filter type (media/electronic cleaner) and the number of filters installed for reminders.

Installer Setup - Filter and Humidifier Reminders

Air Filter and EAC Reminder Setup

Sets reminders for air filter, electronic air cleaner cell, and post-filter replacement.

Humidifier Type and Wiring Configuration

Configures humidifier type (steam, bypass, fan-powered) and wiring for humidification control.

Installer Setup - Humidifier Control Settings

Humidifier Operation Mode Configuration

Configures when the humidifier runs in heat, cool, or off modes, and the fan control method.

Humidifier Pad Reminder Setup

Sets reminders for humidifier pad replacement based on runtime days or calendar months.

Installer Setup - Dehumidification Control Options

Dehumidifier Sensor and Wiring Setup

Selects the sensor for dehumidification and configures dehumidifier wiring options (U terminals).

Dehumidification Over Cooling Limit Setup

Sets the overcooling limit for dehumidification using the AC system, affecting temperature settings.

Installer Setup - Dehumidification Methods and Modes

Dehumidification Minimum On Time and Cooling Droop

Configures minimum compressor run time and cooling droop for effective humidity reduction.

Dehumidifier Operation Mode Configuration

Sets whether the dehumidifier operates in heat, cool, or off modes, and configures fan control.

Installer Setup - Ventilation and Bedroom Settings

Ventilation Options and Control Method Configuration

Configures ventilation types (ERV/HRV, Passive, Fresh Air) and control methods (ASHRAE, Percent On Time).

Number of Bedrooms Setting for Ventilation

Sets the number of bedrooms, used for ASHRAE ventilation calculations in residential applications.

Installer Setup - Ventilation Standards and Lockouts

Ventilation Rate and Priority Configuration

Configures ventilation rate (CFM) and priority (Lockouts vs. ASHRAE) for ventilation control.

Outdoor Condition Ventilation Lockouts

Sets lockouts for ventilation based on outdoor temperature and dewpoint to maintain indoor air quality.

Installer Setup - Ventilation Humidity Lockouts and Reminders

Ventilation Lockouts for Humidity Control

Configures ventilation lockouts during humidity control calls to maintain desired humidity levels.

Ventilator Reminder Configuration

Sets reminders for ventilator core and filter cleaning to ensure optimal system performance.

Installer Setup - Backlighting, Time, and Offset Settings

Backlighting and Clock Format Configuration

Configures backlighting behavior (On Demand/Continuous) and clock format (12/24 hour).

Daylight Saving and Temperature/Humidity Offsets

Manages daylight saving time settings and allows for indoor temperature and humidity offsets.

Installer Tests for System Verification

Accessing Installer Tests

Guides on how to access installer tests via the MENU, Installer Options, and password entry.

Performing Equipment and Wireless Tests

Details how to test equipment and verify wireless communication strength between devices.

Wireless Signal Strength Test and Outdoor Sensor Mounting

Performing the Wireless Signal Strength Test

Describes how to perform the wireless test and interpret signal strength results for reliable communication.

Mounting Outdoor Sensors

Provides instructions for mounting wireless and wired outdoor sensors in optimal locations for accurate readings.

Sensor Mounting Procedures

Wireless Indoor Sensor Mounting Steps

Step-by-step instructions for mounting the wireless indoor sensor, including wallplate attachment.

Wired Indoor Sensor Mounting Steps

Details the process of mounting a wired indoor sensor, including wire routing and wallplate attachment.

Thermostat Operation Overview

Residential Display Quick Reference

Provides a quick reference to the residential display screen, explaining the function of each button and display element.

Remote Control Mounting

Instructions for optionally mounting the Entry/Exit or Vent Boost remote to a wall for convenient access.

Setting Thermostat Time and Date

Adjusting Time and Date Settings

Guides on how to set the current time and date on the thermostat for accurate scheduling and features.

Commercial Display Overview

Explains the commercial display screen, detailing button functions and information shown.

Thermostat Operation: Fan, System Mode, and Schedules

Setting Fan and System Modes

Instructions for selecting fan modes (On, Auto, Circ) and system modes (Heat, Cool, Off, Auto, Em Heat).

Adjusting Program Schedules

Guides on using the scheduling assistant or manually creating program schedules for temperature control.

Schedule Overrides for Residential and Commercial Use

Overriding Residential Schedules

Explains how to temporarily override the programmed schedule with temporary or permanent holds.

Overriding Commercial Schedules

Details how to adjust temperature and hold times for temporary overrides in commercial applications.

Viewing Equipment Status and Vacation Hold

Viewing Equipment Status Information

Shows how to access and view the status of heating, cooling, fan, and IAQ equipment controlled by the thermostat.

Setting Vacation Hold (Residential Use)

Guides on setting vacation mode to save energy while away and restore settings before returning home.

Commercial Scheduling: Holidays and Custom Events

Setting Holiday/Event Schedules (Commercial)

Customizes temperature settings for holidays and special events to conserve energy when the workplace is unoccupied.

Setting Custom Events (Commercial Use)

Allows customization of temperature settings for specific events on selected dates or days of the month.

Commercial Holiday Schedule and Override Settings

Setting Holiday Schedules (Commercial Use)

Customizes temperature settings for specified national holidays, resuming normal scheduling between them.

Setting Holiday Override (Commercial Use)

Allows customizing temperature settings to be maintained until a specified future date, resuming normal scheduling afterward.

Commercial Occupancy, Remote Setback, and Humidification

Initiating Occupancy Mode (Commercial Use)

Enables setting energy-saving temperatures until manually overridden for occupied periods in commercial settings.

Remote Setback Configuration (Commercial Use)

Sets up remote setback using occupancy sensors, including terminal connections and open/closed contact options.

Adjusting Humidification Settings

Guides on setting the desired humidity level and configuring humidification control options.

Humidification Control and Window Protection

Window Protection for Humidification

Limits humidity to prevent frost/condensation on windows, requiring an outdoor sensor for operation.

Dehumidification Settings - Residential Use

Guides on setting dehumidification levels and controlling humidity using AC or a whole house dehumidifier.

Dehumidification and Ventilation Settings Adjustment

Dehumidification Settings - Commercial Use

Guides on setting dehumidification levels and controlling humidity using the AC system or a dehumidifier in commercial applications.

Adjusting Ventilation Settings

Provides instructions for adjusting ventilation settings, including mode, temporary boost, and lockout options.

Ventilation Options and Thermostat Preferences

Ventilation Mode and Control Options

Explains ventilation modes (Auto, Off, On), temporary boost, and lockout settings for air quality management.

Setting Thermostat Preferences

Allows customization of thermostat display and response, including reminders, display options, and clock settings.

Thermostat Screen Cleaning and Security Settings

Cleaning the Thermostat Screen Safely

Describes how to use the Clean Screen option to lock the screen for safe cleaning.

Adjusting Security Settings and Lock Mode

Guides on setting security options like lock mode (Unlocked, Partially, Fully) to prevent unauthorized changes.

Advanced Thermostat Features and Control Algorithms

Viewing Dealer Information

Allows users to view installer contact information for service and support purposes.

Adaptive Intelligent Recovery (Residential)

Explains how the thermostat learns system performance to optimize temperature recovery for comfort.

Proportional Plus Integral (P+I) Control Explained

Details the P+I control algorithm for precise temperature management, differentiating it from conventional thermostats.

Temperature and Humidity Display Interpretation

Understanding Temperature Display Variations

Explains why thermostat temperature readings might differ from ambient, especially with remote sensors.

Interpreting Humidity Display Readings

Clarifies how humidity readings are displayed, especially when using multiple sensors for different controls.

Thermostat Outputs, Inputs, and Data Logs

Thermostat Outputs (U1, U2, U3) Explained

Lists the available outputs for controlling IAQ equipment and heating/cooling stages.

Thermostat Inputs (S1, S2, S3, S4) Explained

Details the inputs for connecting sensors and dry contact devices for system monitoring and alerts.

Data Logs Overview and Usage

Explains the purpose of Data Logs (Alerts Log, User Interactions Log) for troubleshooting and system analysis.

Data Logs and Dry Contact Alert Types

Accessing Data Logs via MicroSD Card

Guides on accessing data logs by downloading them to a microSD card for computer analysis.

Understanding Dry Contact Alert Types

Lists available dry contact alerts such as drain pan, dirty filter, water leak, and system shutdown.

Setting Up Dry Contact Alerts Configuration

Wiring Dry Contact Devices to Terminals

Shows how to wire dry contact devices to S terminals on the EIM or thermostat for alert functionality.

Configuring Dry Contact Alert Settings

Guides on selecting terminals, alert types (normally open/closed), and naming custom alerts.

Custom Alerts and Staging Control Setup

Creating and Customizing Alerts

Details the process of typing alert names and messages for custom dry contact alerts detected by the system.

Staging Control and Differential Settings

Explains staging control based on differentials between stages for balancing comfort and conservation.

Backup Heat Control and Timer Configuration

Backup Heat Droop Configuration

Configures backup heat droop settings to restrict backup heat usage based on indoor temperature drops.

Backup Heat Upstage Timer Setup

Sets the upstage timer for backup heat, determining when backup heat is used based on elapsed time.

Heat Pump and Backup Heat Operation

Multistage Control and Heat Pump Lockouts

Explains multistage control and outdoor temperature lockouts for heat pump and backup heat operation.

Alert Lights and Geothermal Radiant Heat Setup

Understanding Alert Light Indicators

Explains the alert light's behavior for general alerts, heat pump system issues, and emergency heat mode.

Geothermal Radiant Heat Configuration

Guides on setting up geothermal radiant heat control, including stage selection and terminal wiring.

Heating Modes and Introduction to IAQ Control

Heat Pump Backup Heat Modes Explained

Details how backup heat operates in heat pump systems during Heat Mode and Emergency Heat Mode.

Indoor Air Quality (IAQ) Control - Humidification

Introduces IAQ control, focusing on humidification settings and window protection features.

Humidification Setup and Window Protection

Setting Up Humidification Control

Guides on selecting humidifier type, sensors, terminals, and setting window protection for humidity control.

Window Protection for Frost/Condensation Prevention

Explains window protection settings to prevent frost/condensation by limiting humidifier operation.

Humidification Control Options and System Modes

Humidification System Mode Selection

Selects system modes (Heat, Cool, Auto) that allow humidification, detailing conditions for operation.

Humidification Control Options (ISU 807)

Configures humidifier control options like 'Hum when Heat is On' and 'Tstat Controls Fan' for desired humidity.

Dehumidification Control Methods and Residential Setup

Dehumidification Settings - Residential Use

Guides on setting dehumidification levels and controlling humidity using AC or a whole house dehumidifier.

Dehumidification Using Cooling System

Explains how to use the AC system for dehumidification, including overcooling limits and U terminal wiring.

Dehumidification with Cooling System Configuration

Setting Up Dehumidification with AC System

Guides on selecting dehumidification equipment, sensors, terminals, and overcooling limits for AC-based dehumidification.

Whole House Dehumidifier Setup Procedure

Whole House Dehumidifier Configuration

Details setting up a whole house dehumidifier, including equipment selection, sensor choice, and mode selection.

Dehumidification Away Mode and Fan Control Settings

Dehumidification Away Mode Setup

Configures Dehumidification Away Mode for commercial applications to maintain humidity during unoccupied periods.

Dehumidifier Fan Control Options

Sets dehumidifier fan control options (Tstat Controls Fan, Equip Controls Fan) for optimal dehumidification.

Dehumidification Control Levels and Commercial Settings

Commercial Dehumidification Settings

Guides on setting dehumidification levels for commercial applications using AC or a dehumidifier.

Dehumidification Using Cooling System Methods

Explains dehumidification methods using AC systems like Low Fan, High Fan, or Hot Gas Bypass.

Dehumidification Methods and Cooling System Integration

Minimum On Time, Cooling Droop, and Reheat

Details dehumidification methods like minimum on time, cooling droop, and reheat for humidity control.

Setup Dehumidification with Cooling System

Guides on setting up dehumidification using the cooling system, including sensor and terminal configurations.

Dehumidification with Cooling System Configuration Details

Cooling System Dehumidification Terminal and Control Setup

Covers terminal wiring and dehumidification control settings for cooling systems and dry contact devices.

Dehumidifier Setup and Away Mode Configuration

Whole House Dehumidifier Setup

Details setting up a whole house dehumidifier, including equipment selection, sensor choice, and mode selection.

Dehumidification Away Mode Explanation

Explains Dehumidification Away Mode for commercial applications, maintaining humidity during unoccupied periods.

Ventilation Options and Thermostat Preferences

Ventilation Options and Control Method Configuration

Configures ventilation types (ERV/HRV, Passive, Fresh Air) and control methods (ASHRAE, Percent On Time).

Setting Thermostat Preferences

Allows customization of thermostat display and response, including reminders, display options, and clock settings.

Ventilation Control and Outdoor Condition Lockouts

Ventilation Control Methods and Priority

Explains ventilation control methods (ASHRAE, Percent On Time) and priority settings for lockouts.

Outdoor Condition Ventilation Lockouts

Sets lockouts for ventilation based on outdoor temperature and dewpoint to maintain indoor air quality.

Ventilation Setup - Fan Control and Priority

Ventilation Fan Control and Rate Settings

Configures ventilation fan control and rate (CFM), ensuring compliance with ASHRAE 62.2 standards.

Ventilation Priority Selection

Sets ventilation priority between lockouts and ASHRAE standards for optimal air quality management.

Ventilation Priority and Percent On Time Configuration

Ventilation Priority Options Explained

Details ventilation priority settings: Lockouts Priority vs. ASHRAE Priority, and their implications.

Ventilation Percent On Time Setup

Configures the percentage of time ventilation equipment runs to meet desired air exchange rates.

Ventilation Lockouts and Humidity Ventilation

Lockout Ventilation Calls for Humidity Control

Configures ventilation lockouts during humidity control calls to maintain desired humidity levels.

Ventilate on High Indoor Humidity

Enables ventilation when indoor humidity is high, particularly in heat mode, to remove excess moisture.

Ventilation Options and IAQ Reminders Setup

Ventilation Mode and Temporary Boost Settings

Sets ventilation modes (Auto, Off, On) and temporary boost duration for ventilation control.

IAQ Reminders Configuration

Allows setting IAQ reminders for filter changes, pad cleaning, and bulb replacements.

Customizable Reminders Configuration

Setting Standard Reminders

Guides on setting reminders for service, spring/fall maintenance, and warranty renewals for system upkeep.

Creating Custom Reminders

Enables creation of custom reminders for system maintenance or warranty, including date or temperature triggers.

MicroSD Card Usage for Setup and Data Management

Loading Custom Reminders and Data Logs

Explains how to load custom reminders and save data logs to a microSD card for transfer and analysis.

MicroSD Card for Software and Dealer Info

Details using a microSD card to upgrade thermostat software and load dealer information.

Thermostat Software and Dealer Information Management

Updating Thermostat Software via MicroSD

Guides on downloading and installing thermostat software upgrades using a microSD card.

Loading Dealer Information via MicroSD

Explains how to upload dealer contact information to the thermostat via a microSD card for user support.

Commercial Features and Schedule Overrides

Commercial Application Features Overview

Lists features specific to commercial applications, including language, overrides, ramp rates, and holiday schedules.

Overriding Schedules in Commercial Use

Details how to adjust temperature and hold times for temporary overrides in commercial applications.

Commercial Scheduling: Holidays and Custom Events

Setting Holiday/Event Schedules (Commercial)

Customizes temperature settings for holidays and special events to conserve energy when the workplace is unoccupied.

Setting Custom Events (Commercial Use)

Allows customization of temperature settings for specific events on selected dates or days of the month.

Commercial Holiday Schedule and Override Settings

Setting Holiday Schedules (Commercial Use)

Customizes temperature settings for specified national holidays, resuming normal scheduling between them.

Setting Holiday Override (Commercial Use)

Allows customizing temperature settings to be maintained until a specified future date, resuming normal scheduling afterward.

Commercial Occupancy Mode and Ramp Rate Settings

Initiating Occupancy Mode (Commercial Use)

Enables setting energy-saving temperatures until manually overridden for occupied periods in commercial settings.

Ramp Rates (Commercial Use) Explained

Explains ramp rates for recovery, allowing thermostats to adjust based on outdoor conditions for energy savings.

Commercial Remote Setback Configuration

Remote Setback Setup (Commercial Use)

Sets up remote setback using occupancy sensors, including terminal connections and open/closed contact options.

Economizer and Time of Day (TOD) Operation

Economizer Module Control Explained

Explains how the thermostat controls the economizer module for ventilation and free cooling based on conditions.

Pre-Occupancy Purge Setup

Configures pre-occupancy purge to run the fan before occupied periods, ensuring comfortable workplace arrival.

Optional Accessories Overview and Setup

Portable Comfort Control Functionality

Describes the portable remote control for adjusting temperature in different rooms or multiple thermostats.

Wireless Sensors and Remotes Overview

Details wireless outdoor/indoor sensors, internet gateway, and entry/exit/vent boost remotes for enhanced control.

Remote Indoor Sensor Operation and Configuration

Temperature Control with Remote Sensors

Explains how thermostats use internal and remote sensors for temperature control, including averaging.

Humidification and Dehumidification Sensor Selection

Guides on selecting sensors for humidification and dehumidification, and naming sensors for proper identification.

Wireless Indoor Sensor Operations and Display

Wireless Indoor Sensor Functions and Battery Status

Describes sensor functions, battery indicators, and temperature display behavior on the thermostat.

Temperature Display Interpretation

Explains why thermostat temperature readings might differ from ambient, especially with remote sensors.

Humidity Display and Sensor Selection Details

Humidity Display Interpretation

Clarifies how humidity readings are displayed, especially when using multiple sensors for different controls.

Selecting Humidity Sensor for Home Screen Display

Allows selection of which humidity sensor reading to display on the home screen from multiple sensors.

Outdoor Sensor Wiring Guide

Wiring C7089U1006 Outdoor Sensor

Provides instructions for wiring the C7089U1006 Outdoor Sensor to S terminals, including cable and mounting guidance.

Wired Indoor Sensor Wiring Guide

Wiring C7189U1005 Indoor Sensors

Details wiring configurations for C7189U1005 sensors for temperature averaging, including 10K/20K selection.

Wiring TR21 and TR21-A Sensors

Provides wiring diagrams for TR21 and TR21-A sensors, including instructions for 10K/20K selection and series wiring.

Zoning Wiring Diagrams

VisionPRO Thermostats with HZ432 Zone Panel

Shows wiring diagrams for VisionPRO thermostats connected to an HZ432 zone panel for zoning control.

Zoning and Humidification Wiring Integration

HZ432 Zone Panel and TrueSTEAM Humidifier Wiring

Illustrates wiring for a VisionPRO thermostat controlling a zone panel and a TrueSTEAM humidifier.

Zoning Ventilation and Dehumidification Wiring

Ventilator Wiring with HZ432 Zone Panel

Shows wiring for a ventilator connected to an HZ432 zone panel and VisionPRO thermostat for ventilation control.

Dehumidifier Wiring with HZ432 Zone Panel

Illustrates wiring for a TrueDRY dehumidifier connected to an HZ432 zone panel and VisionPRO thermostat.

Frequently Asked Questions (FAQs)

Zoned System Control FAQs

Answers questions about how VisionPRO controls humidifiers, ventilators, and dehumidifiers in zoned systems.

Zone Panel and Sensor Compatibility FAQs

Discusses compatibility with zone panels (HZ322, HZ432) and the use of remote sensors with zoning.

Troubleshooting and Regulatory Compliance

Troubleshooting Common Thermostat Issues

Provides solutions for common issues like blank screen, difficult readability, red light, and system non-response.

FCC Compliance and Warnings

Details FCC compliance statements and warnings for the thermostat, EIM, and portable comfort control.