EasyManua.ls Logo

Honeywell 5806W3 - User Manual

Honeywell 5806W3
4 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
General Information
Before installing detectors, please thoroughly read these installation
instructions and Guide for Proper Use of System Smoke Detectors
(A05-1003-002), which provides detailed information on detector
spacing, placement, zoning, wiring, and special applications. Copies
of this manual are available from Honeywell.
NOTICE: This manual should be left with the owner/user of
this equipment.
IMPORTANT: This detector must be tested and maintained regularly
following NFPA 72 requirements. The detector should be cleaned at
least once a year.
General Description
The 5806W3 photoelectronic smoke detector with built-in wireless
transmitter is intended for use with wireless alarm systems that
support 5800 series devices. Refer to control/communicator installation
instructions for compatibility. The 5806W3 smoke detector can be
used with any 5800 series wireless receiver/transceiver for residential
installations. For commercial installations, the 5881ENHC or
the 5883H receiver is required. The transmitter can send alarm,
tamper, maintenance (when control panels are equipped to process
maintenance signals), and battery condition messages to the system’s
receiver. The maintenance signal fully complies with the sensitivity
test requirement specified in NFPA 72, 7-2.2 and is approved by UL.
Refer to the wireless system’s instructions for the maximum number
of transmitters that can be supported.
The 5806W3 incorporates a state-of-the-art optical sensing chamber
and an advanced microprocessor. The microprocessor allows the
detector to automatically maintain proper operation at factory
calibrated detection levels, even when sensitivity is altered due to the
presence of contaminants settling into the unit’s smoke chamber. In
order for this feature to work properly, the chamber must never be
opened while power is applied to the smoke detector. This includes
cleaning, maintenance or screen replacement.
The 5806W3 contains a piezoelectric horn which generates the ANSI
S3.41 temporal pattern in an alarm condition. In alarm, a message is
also sent to the wireless control panel and the smoke detectors zone
number is displayed at the console. The alarm message is transmitted
every 4 seconds until the smoke condition has cleared and the
detector has reset. During an alarm condition, pressing the detector’s
test switch will silence the piezoelectric horn for 5 minutes. Once
the detector has reset, a RESTORE message is transmitted to the
control panel and the transmitters zone number can be cleared from
the panel. The built-in Drift Compensation algorithm automatically
maintains the sensitivity of the detector. Once the detector reaches its
limit of compensation, it transmits a maintenance signal to the panel.
The mounting base installation is simplified by the incorporation of
features compatible with drywall fasteners or other methods that
provide a method for securing the detector in place.
5806W3 Photoelectronic Smoke Detector
with Built-in Wireless Transmitter
INSTALLATION AND SETUP GUIDE
I56-3022-004R
Two LEDs and a sounder on the detector provide local visual and
audible indication of the detectors status:
Table 1: Detector LED Modes
Green LED Red LED
Piezoelectric
Horn
Power Up
Blinks every
5 sec
Blinks every
5 sec
Off
Normal (standby)
Blinks every
10 sec
Off Off
Out of Sensitivity Off
Blinks every
5 sec
Off
Smoke Alarm Off
Blinks every
1 sec
Temporal Pattern
Low Battery Off
Blinks every
45 sec
Chirp every 45
sec after LED
blinks for 7 days
During initial power-up, the red and green LEDs will blink
synchronously once every 5 seconds. It will take approximately 20
seconds for the detector to finish the power-up cycle (see Table 1).
After power-up has completed and the detector is functioning normally
within its listed sensitivity range, the green LED blinks once every
10 seconds. If the detector is in need of maintenance because its
sensitivity has shifted outside the listed limits, the red LED blinks
once every 5 seconds. When alarm has been activated by smoke, the
red LED blinks every 1 second. The LED indication must not be used
in place of the tests specified under Testing. If the detector senses a
low battery condition, the red LED blinks once every 45 seconds.
To measure the detectors sensitivity, the i3 Series Model SENS-RDR
Infrared Sensitivity Reader tool (see Figure 4) should be used. Refer to
instruction manual D100-98-00 for proper use of the SENS-RDR.
Low Battery Detection
The 5806W3 is powered by a single 3-volt CR123A or DL123A Lithium
battery (included). The detector checks for a low battery at least
every 65 minutes. If a low battery is detected, the transmitter sends
a low battery message to the control panel, which beeps and displays
the detectors zone number. In addition, the red LED of the 5806W3
will blink every 45 seconds and the test switch will be disabled. This
condition will exist for a minimum of 7 days, and then the detectors
horn will “chirp” about every 45 seconds. Pressing the test switch
during this time will silence the chirps for 12 hours. The battery
should be replaced BEFORE the chirps begin. Be sure to replace the
battery with a fresh one.
- 1 -
Question and Answer IconNeed help?

Do you have a question about the Honeywell 5806W3 and is the answer not in the manual?

Summary

General Information

Detector LED Modes

Details visual and audible status indications provided by the detector's LEDs and sounder.

Low Battery Detection

Explains how the detector identifies, signals, and manages low battery conditions.

Battery Installation and Replacement

Programming

Steps for enrolling the smoke detector's serial number into the control panel system.

Mounting

Instructions for selecting a location and physically installing the detector base and unit.

Tamper Protection

Testing the Sensor

Explains methods for testing the smoke detector's functionality using test switches or smoke.

Testing Signal Strength

Details how to test the wireless communication path between the detector and the control panel.

Testing Programmed Loops

Describes testing to ensure all programmed loops transmit correctly to the system.

Maintenance

Specifications

Lists the technical specifications of the smoke detector, including power, dimensions, and operating conditions.

Summary

General Information

Detector LED Modes

Details visual and audible status indications provided by the detector's LEDs and sounder.

Low Battery Detection

Explains how the detector identifies, signals, and manages low battery conditions.

Battery Installation and Replacement

Programming

Steps for enrolling the smoke detector's serial number into the control panel system.

Mounting

Instructions for selecting a location and physically installing the detector base and unit.

Tamper Protection

Testing the Sensor

Explains methods for testing the smoke detector's functionality using test switches or smoke.

Testing Signal Strength

Details how to test the wireless communication path between the detector and the control panel.

Testing Programmed Loops

Describes testing to ensure all programmed loops transmit correctly to the system.

Maintenance

Specifications

Lists the technical specifications of the smoke detector, including power, dimensions, and operating conditions.

Overview

The Honeywell 5806W3 is a photoelectronic smoke detector equipped with a built-in wireless transmitter, designed for use with wireless alarm systems that support 5800 series devices. It is compatible with any 5800 series wireless receiver/transceiver for residential installations, and for commercial applications, requires the 5881ENHC or 5883H receiver. This detector is capable of transmitting alarm, tamper, maintenance, and battery condition messages to the system's receiver. The maintenance signal adheres to NFPA 72, 7-2.2 sensitivity test requirements and is UL approved.

At its core, the 5806W3 utilizes a state-of-the-art optical sensing chamber and an advanced microprocessor. This microprocessor enables the detector to automatically maintain optimal operation at its factory-calibrated detection levels. This is achieved even when sensitivity is affected by contaminants accumulating in the smoke chamber, thanks to a built-in Drift Compensation algorithm. For this feature to function correctly, the chamber must never be opened while the smoke detector is powered, which includes during cleaning, maintenance, or screen replacement.

The detector provides local visual and audible indications of its status through two LEDs (green and red) and a piezoelectric horn. During initial power-up, both LEDs blink synchronously every 5 seconds for approximately 20 seconds. Once the power-up cycle is complete and the detector is operating normally within its listed sensitivity range, the green LED blinks once every 10 seconds. If the detector requires maintenance due to its sensitivity shifting outside the listed limits, the red LED blinks once every 5 seconds. In a smoke alarm condition, the red LED blinks every 1 second, and the piezoelectric horn emits the ANSI S3.41 temporal pattern. If a low battery condition is detected, the red LED blinks every 45 seconds. The LED indications are supplementary and should not replace the specified testing procedures.

The piezoelectric horn generates the ANSI S3.41 temporal pattern during an alarm. When an alarm occurs, a message is sent to the wireless control panel, and the detector's zone number is displayed on the console. Alarm messages are transmitted every 4 seconds until the smoke condition clears and the detector resets. During an alarm, pressing the detector's test switch will silence the horn for 5 minutes. Once the detector resets, a RESTORE message is transmitted to the control panel, allowing the transmitter's zone number to be cleared from the panel. When the detector reaches its compensation limit, it transmits a maintenance signal to the panel.

The 5806W3 is powered by a single 3-volt CR123A or DL123A Lithium battery (included). The detector performs a low battery check at least every 65 minutes. Upon detecting a low battery, the transmitter sends a low battery message to the control panel, which then beeps and displays the detector's zone number. Additionally, the red LED of the 5806W3 will blink every 45 seconds, and the test switch will be disabled. This low battery condition persists for a minimum of 7 days, after which the detector's horn will "chirp" approximately every 45 seconds. Pressing the test switch during this chirping period will silence the chirps for 12 hours. It is recommended to replace the battery before the chirping begins with a fresh one.

Installation of the mounting base is simplified by features compatible with drywall fasteners or other securing methods. For mounting, first determine the optimal location for strong wireless transmission and proper smoke detection. A good transmission path must be established from the proposed mounting location before permanent installation. The detector's serial number must be "enrolled" into the system prior to mounting. The mounting base can be installed on the ceiling or wall (if local ordinances permit) using the provided screws and anchors. The detector is then turned clockwise onto the mounting base until it clicks into place. The detector must not be attached to removable ceiling panels; instead, it should be attached across a panel support.

The smoke detector must be enrolled in the control panel for system operation. The 5806W3 smoke protection zone must be enrolled as Loop 1 with an "Input Type" of 3 (supervised RF). The detector can also monitor Maintenance (transmitted as Loop 2) and Tamper (transmitted as Loop 4). To utilize the Maintenance feature, each loop must be programmed as a separate zone in the 5800 series wireless compatible panel. Loop 1 (Smoke) should be programmed as a Fire zone (type 9 or 16), and Loop 2 (High/Low Maintenance) as a 24-Hr. Trouble zone (type 19). Loop 2 High/Low Maintenance is supported only on commercial control panels like the Vista-128FBP. Input Type 03 (3 on some controls) is used for the supervised RF Transmitter. To transmit the serial number during programming, the tamper switch is activated by rotating the detector counter-clockwise on its base until it snaps open, then returning it to the clockwise position until it snaps into place. The fire protection zone enrolled must always be Loop 1; otherwise, fire annunciations will not be reported by the control.

The detector includes a built-in tamper switch that triggers a CHECK signal at the console if the detector is removed from its mounting base. A tamper-resistant feature prevents removal without a tool. To engage this feature, a small plastic tab on the mounting base (Figure 2) must be cut off before installing the detector. To remove a tamper-resistant detector, a small screwdriver is used to depress the square tamper release tab on the skirt of the mounting base, then the detector is turned counter-clockwise.

Testing the sensor is crucial. Before testing, the central station must be notified that the smoke detector system is undergoing maintenance to prevent unwanted alarms. During initial power-up, SENS-RDR or canned smoke should not be used. These methods can be used after the power-up sequence is complete. Detectors must be tested after installation and following periodic maintenance. Testing methods include:

  1. Test Switch: A recessed test switch is located on the detector housing. Pushing and holding this switch for a minimum of 5 seconds with a small screwdriver or Allen key (max diameter 0.18 inch) will trigger the alarm panel and cause the smoke detector to alarm. If the tool is removed, the sounder will shut off. If the detector is within sensitivity limits, the LED will blink once per second, and the horn will sound within 3 seconds.
  2. Smoke Entry Test: Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow smoke through it until the unit alarms. Canned aerosol is also an acceptable method. Smoke detection testing verifies system protection capability. A detector failing this test should first be cleaned as outlined in the maintenance section. If it still fails, it should be returned for repair.

Signal strength testing should be performed according to NFPA 72 requirements to ensure a strong communication path with the control panel. This involves activating the wireless system's GO/NO GO TEST mode from the keypad, then depressing and holding the smoke detector's TEST switch. If the detector is within proper sensitivity limits and has not detected a low battery, it should immediately transmit an alarm signal. The built-in horn will sound about 2.5 seconds after pressing the button. The wireless system's keypad should emit at least three audible sounds upon receiving the alarm transmission and display the transmitting detector's zone number. Releasing the TEST switch will stop the horn, and the zone number will clear from the console display. If the console does not respond, check battery polarity and freshness. For initial installations, try moving the detector to another location for better reception and ensure the detector has been "enrolled" by the control panel. The system's TEST mode should then be turned off from the keypad.

Programmed loops should be tested before installation to ensure all intended loops are operational. This involves activating the system's TRANSMITTER ID SNIFFER mode from the keypad. All programmed wireless zones will be displayed sequentially on the keypad. After mounting the detector, pressing its TEST switch should cause all zones associated with the smoke detector to disappear from the keypad on the next display cycle, indicating successful transmission from each programmed loop. Once testing is complete, the Installer code + OFF key exits TEST mode. After all system testing, the central station should be notified that the system is back online.

Maintenance procedures require notifying the proper authorities and the central station that maintenance is being performed and the system will be temporarily out of service. The zone or system undergoing maintenance should be disabled to prevent unwanted alarms. The procedure involves:

  1. Removing the detector housing from the base by twisting counter-clockwise.
  2. Removing the battery from the unit.
  3. Waiting 20 seconds to ensure proper power-down sequence.
  4. Removing the detector cover by turning counter-clockwise.
  5. Vacuuming the cover or using canned air to remove dust or debris.
  6. Removing the top half of the screen/sensing chamber by lifting straight up.
  7. Vacuuming or using canned air to remove any dust or particles from all chamber sections.
  8. Replacing the top half of the screen/sensing chamber by aligning the arrow on the screen/sensing chamber with the arrow on the housing, pressing down firmly until it is fully seated.
  9. Replacing the detector cover by placing it over the screen/sensing chamber and turning it clockwise until it snaps into place.
  10. Reinstalling the battery into the battery compartment, noting proper orientation. The red and green LEDs will flash once every 5 seconds for approximately 20 seconds until the power-up cycle is complete.
  11. Reinstalling the detector and testing it.
  12. Notifying the central station when the system is back in service. If this procedure is not followed exactly, the detector may indicate a maintenance trouble after power-up. If this occurs, the battery should be removed for 20 seconds and then reinstalled. Dust covers are effective in limiting dust entry during construction, but detectors should be removed before construction or other dust-producing activities. When returning the system to service, dust covers must be removed. Smoke detectors should not be used with detector guards unless the combination has been evaluated and found suitable.

Honeywell 5806W3 Specifications

General IconGeneral
Alarm Sound Level85 dB
Temperature Range40°F to 100°F
Wireless CompatibilityYes
Operating Voltage3V
Operating Frequency345 MHz
Power SourceBattery
CompatibilityHoneywell Wireless Systems
Range200 ft (61 m) open air

Related product manuals