10
*80 OUTPUT DEFINITION MODE
(press
80 while in Data Programming mode)
Output Funct. #
(00 = Quit) 01
Enter the output function number to be defined
01-12 = output function number
[] to continue; 00 = exit
01 A E Trig
?00 0 0 ZL=00
This screen displays a summary of the current output programming
A = Output Action; E = Triggering event; Trig = Trigger type
Question mark indicates the device shown has not been mapped. Use *79 Menu mode to map the device.
[] to continue
01 Activated By:
Zone List
Select where the initiating event for this output definition is to occur.
0 = delete (deletes the output function and any previous programming)
Delete? To delete this output definition, press 1.
0 = NO, 1 = YES If you do not want to delete this output,. press 0.
1 = zone list (go to A prompt); 2 = zone type (go to B prompt); 3 = zone number (go to C prompt)
[] to continue
A
01 Zn List
1
If zone list was selected, this screen appears. Otherwise skip to the next prompt.
Enter the desired zone list number associated with this output number:
01-08 = zone list (Do not use pager zone list 09 in output definitions)
Enter the zone list event that will activate this output:
Enter Event 0 = restore; 1 = alarm;
Alarm 1 2 = fault; 3= trouble
NOTE: For alarm, fault, and trouble, an event on ANY zone in the list activates the output, but ALL zones in
the list must be restored before the output is restored.
Press [] to continue and skip to the Output Action prompt.
B
01 Enter Zn type
Perimeter 03
If zone type was selected, this screen appears. Otherwise skip to the next prompt.
Enter the desired zone type for this output number. See list below *80 Worksheet for zone types.
Press [] to continue and skip to the Output Action prompt.
C
01 Enter Zn No.
12
If zone number was selected, this screen appears.
Enter the desired zone number associated with this output number.
Press [] to continue.
Enter the zone event that will activate this output.
01 Enter Event 0 = restore; 1 = alarm/fault/trouble
Restore 0
Press [] to continue to the Output Action prompt
01 Output Action
Close for 2 sec 1
Enter the desired device action as listed below.
0 = off 4 = Change Device State
1 = Close for 2 seconds 5 = Duration 1 (see data field *177)
2 = Stay Closed 6 = Duration 2 (see data field *177)
3 = Pulse 1 sec ON, 1 sec OFF
Press [] to continue.
Enter Output No.
R02 02
Enter the device output number (programmed in *79 Menu Mode) you want associated with this output.
01-04 = output no.
17-18 = on-board triggers
Press [] to continue.
02 A E P TRIG
R02 1 1 3 ZL=1
A summary screen appears showing the programmed settings.
Press [] to return to output function number prompt.
*81 ZONE LIST PROGRAM MODE (press
81
while in Data Programming mode)
Zone List No.
(00 = Quit) 01
Enter the Zone List Number to program (or 00 to end these entries).
01-09 = zone list number
[] to continue
01 Enter Zn Num.
(00 = Quit) 00
Enter each zone number followed by [] to add each zone to the zone list.
01-06 = wired zones; 09-24 = wireless zones; 49-56 = button zones
91 = addr. device report enable (Enter a report code for zone 91 to enable addressable device reporting.
92 = duress report enable (Enter a report code for zone 92 to enable duress reporting)
95, 96, 99 =emergency zones
00 to continue
IMPORTANT: Do not include fire zones in zone lists that are used to STOP device actions.
01 Del Zn List?
0 = No 1 = Yes 0
0 = dont delete list; current zone list remains saved
1 = delete this zone list; All zones in the zone list will be deleted automatically and the system returns to the
Zone List No. prompt.
[] to continue
WWW.DIYALARMFORUM.COM