9-3
V48D-SOC-V2
EARTH
GROUND
SEE
INSTRUCTIONS
FOR PROPER
GROUNDING
TELEPHONE WIRING
(VIA RJ31X JACK AND DIRECT CONNECT CORD)
WARNING:
TO PREVENT RISK OF SHOCK, DISCONNECT
TELEPHONE LINE AT TELECOM JACK BEFORE SERVICING THIS UNIT.
RING
(GRAY)
TIP
(GREEN)
RING
(RED)
INCOMING
PHONE LINE
HANDSET
TIP
(BROWN)
}
}
CLASS 2 PLUG-IN TRANSFORMER
16.5VAC, 25VA MINIMUM
OUTPUT FOR 110VAC
(e.g. ADEMCO No. 1321)
OR
WIRED-IN 16.5VAC,
25VA MINIMUM
220VAC TRANSFORMER
TO
110/220VAC
UNSWITCHED
OUTLET (24HR)
+
BATTERY CAPACITY FOR EMERGENCY
BURGLARY STANDBY USE AT LEAST 4 HRS
FOR COMPLETE
INFORMATION,
SEE INSTRUCTIONS
K0749-4EN
ALARM OUTPUT
10.513.8VDC, 2A MAX.
(600mA MAX.
FOR UL USAGE,
INCLUDING AUX POWER)
STEADY FOR
BURGLARY/PANIC,
TEMPORAL PULSE
SOUNDING FOR FIRE.
CAN USE ADEMCO No. 702
SIREN, OR 12V BELL.
SEE INSTRUCTIONS.
CHARGING VOLTAGE
13.8VDC. MAXIMUM
CHARGING CURRENT
650mA.
BATTERY
12V, 4AH
MINIMUM
+
+
BLACK
RED
SEALED LEAD-ACID TYPE.
BATTERY NORMALLY NEED NOT BE
REPLACED FOR AT LEAST 3 YRS.
TO DETERMINE TOTAL STANDBY LOAD
ON BATTERY, ADD 100mA TO TOTAL OF
AUX. POWER OUTPUT AND REMOTE
KEYPAD CURRENTS.
FLYING LEADS
FOR BATTERY
CONNECTION
AUX. POWER
OUTPUT
10.5-13.8VDC
600mA MAX.
(500mA MAX.
FOR UL
INSTALLATIONS)
ALL OUTPUTS
ARE POWER
LIMITED.
OPTIONAL
FOR UP TO 40 ADDITIONAL ZONES
( FROM EITHER OR BOTH GROUPS)
ADEMCO 5800 SERIES
RF RECEIVER
WIRELESS ZONES
BLK
RED
GRN
YEL
8
11
12
17
20
21 22 23 24 25
BLACK: KEYPAD
GROUND (- ) RETURN
RED: KEYPAD PWR ( + )
GREEN: DATA IN FROM KEYPAD
YELLOW: KEYPAD DATA OUT
REMOTE
KEYPADS
AND OTHER
ADDRESSABLE
DEVICES
(e.g. 7845C, 4204,
4219, 4229,
5800 SERIES, 7845i
RECEIVERS)
BLK
RED
GRN
YEL
TO TERM 4
TO TERM 5
TO TERM 6
TO TERM 7
BLK
RED
GRN
YEL
AND/OR
+
ZONE 1
ZONE 2
HI
LO
HI
LO
ZONE 3
ZONE 4
HI
LO
HI
LO
ZONE 5
ZONE 6
HI
LO
HI
LO
ZONE 7
ZONE 8
HI
LO
HI
LO
MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC (PROGRAMMABLE)
8-PIN CONNECTOR
USED FOR
XM10E POWERLINE INTERFACE
CONNECTIONS AND FOR
ON-BOARD TRIGGERS.
SEE INSTRUCTIONS.
78
(USE
SA4120XM-1
CABLE)
CAN BE USED FOR 2-WIRE SMOKE DETECTORS
ASSEMBLED IN MEXICO
NOTE:
KEYPAD (S)
CURRENT
(IN ALL
PARTITIONS)
AND ALL
OTHER DEVICES
DRAWING
POWER FROM
TERMS 4 & 5
MUST BE
INCLUDED IN
AUX CURRENT
DRAIN
CALCULATIONS.
}
2000
OHMS
EOLR
2000
OHMS
EOLR
2000
OHMS
EOLR
2000
OHMS
EOLR
2000
OHMS
EOLR
2000
OHMS
EOLR
2000
OHMS
EOLR
2000
OHMS
EOLR
SYNC
COM
DATA
TO
TRANS.
GND
+12 AUX
18
19
16
15
14
13
10
9
1234 5 6
OUTPUT 18
(TRIG. 2)
OUTPUT 17
(TRIG. 1)
BATTERY FUSE
FOR REPLACEMENT,
USE SAME VALUE
(e.g. ADEMCO No. 90-12)
3A
4-WIRE SMOKE DETECTOR CONNECTIONS
SET
RECEIVERS
DIP SWITCH
FOR DEVICE
ADDRESS
OF 0.
SEE
INSTRUCTIONS.
SET UNITS
DIP SWITCH
FOR DEVICE
ADDRESSES
7 - 15
SEE
INSTRUCTIONS.
MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16;
DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".
ZONE
PAIRS
2 / 10
3 / 11
4 / 12
5 / 13
6 / 14
7 / 15
8 / 16
1312 14
10 11
6.2k
ZONE 10
3k
ZONE 2
2k
2k
2k
ZONE 3
2k
2k
2k
ZONE 4
TAMPER
CONTACTS
TAMPER
CONTACTS
REMOTE KEYPADS
CAN USE 6128RF,
6148 OR 6164 KEYPADS.
(FIRST KEYPAD MUST BE
SET TO ADDRESS 16.)
POWER SHUTDOWN NOTE:
SYSTEM SHUTS DOWN SENSOR
DETECTION PROCESSING IF
CONTROL'S VOLTAGE DROPS
BELOW 9.6V.
+
+
2000
OHMS
EOLR
HEAT
DETECTOR
RED
EOL
POWER
SUPERVISION
RELAY MODULE
A77-716B.
USE N.O.
CONTACT,
WHICH CLOSES
WHEN POWER
IS APPLIED.
VIOLET
AUX PWR
OUTPUT
TERMINALS
5
4
_
_
+
BLK
_
TO ZONE TERM. ( )
TO ZONE TERM. ( )
RELAY
CONTACT OPENS MOMENTARILY
UPON FIRE ALARM RESET
PROGRAM
RELAY
AS ZONE
TYPE 54
(FIRE ZONE
RESET)
_
+
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
N.C.
N.O.
TO OUTPUT 17
PROGRAM OUTPUT 17
FOR "OUT NORM
LOW" = YES IN 79 MENU
MODE AND AS ZONE
TYPE 54 IN
80 MENU MODE
OR
ADEMCO VISTA-48D
SUMMARY OF CONNECTIONS
3
7
6
5
4
21
TYPICAL WIRING FOR ZONE
DOUBLING (CAN ONLY BE
USED ON ZONES 2-8)
TYPICAL WIRING FOR DOUBLE
BALANCED ZONE (CAN ONLY BE
USED ON ZONES 2-8)
RED JUMPER
CUT FOR SIREN SUPERVISION.
ALSO, CONNECT 2000 OHM
RESISTOR DIRECTLY ACROSS
SOUNDER. DO NOT CUT FOR
SELF-ACTIVATED SIREN OUPUT.
ADEMCO No. 6164
WITH 4 ZONES PLUS 1 RELAY
-OR-
ADEMCO No. 4219
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
-OR-
ADEMCO No. 4229
WIRED EXPANSION/RELAY MODULE
(8 ADD'L EOLR WIRED ZONES PLUS 2
OUTPUT RELAYS)
-OR-
ADEMCO No. 4204 RELAY MODULE
(4 OUTPUT RELAYS)
THIS EQUIPMENT SHOULD BE INSTALLED
IN ACCORDANCE WITH THE NATIONAL
FIRE PROTECTION ASSOCIATION'S
STANDARD 72, CHAPTER 2 (NATIONAL
FIRE PROTECTION ASSOCIATION,
BATTERY-MARCH PARK, QUINCY,MA
02269).
PRINTED INFORMATION
DESCRIBING PROPER INSTALLATION,
OPERATION,TESTING, MAINTENANCE,
EVACUATION PLANNING AND REPAIR
SERVICE IS TO BE PROVIDED WITH THIS
EQUIPMENT.
CONNECTION OF THE FIRE ALARM
SIGNAL TO A FIRE ALARM
HEADQUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH THE
PERMISSION OF THE LOCAL AUTHORITY
HAVING JURISDICTION. THE BURGLAR
ALARM SIGNAL SHALL NOT BE
CONNECTED TO A POLICE EMERGENCY
NUMBER.
FOR UL INSTALLATIONS, 110 VAC
TRANSFORMER MUST BE USED
24-HR BATTERY STANDBY REQUIRED FOR
FIRE INSTALLATIONS. USE 12V, 17.2AH
BATTERY FOR 600mA AUX POWER. SEE
INSTRUCTIONS.
USE UL LISTED LIMITED ENERGY
CABLE FOR ALL CONNECTIONS
WEEKLY TESTING IS REQUIRED TO
ENSURE PROPER OPERATION OF
THIS SYSTEM. IN ADDITION, THIS
SYSTEM MUST BE CHECKED BY A
QUALIFIED TECHNICIAN AT LEAST
ONCE EVERY THREE (3) YEARS.
CIRCUIT
(ZONE)
CONTROL UNIT
DELAY-SEC
SMOKE DETECTOR
MODEL DELAY-SEC
USE THE DELAY TIME MARKED ON THE
INSTALLED DETECTOR(S).
ALARM VERIFICATION, IF USED, DELAYS
ALARM SIGNALS FROM THE INDICATED FIRE
CIRCUITS. DO NOT EXCEED 60 SECONDS OF
TOTAL DELAY (CONTROL UNIT PLUS SMOKE
DETECTORS). DO NOT CONNECT OTHER
INITIATING DEVICES TO THESE CIRCUITS
UNLESS APPROVED BY THE LOCAL
AUTHORITY HAVING JURISDICTION.
WARNING
12 secs
Figure 17. VISTA-48D Summary of Connections