EasyManua.ls Logo

Honeywell C7110A1010 User Manual

Honeywell C7110A1010
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
® U.S. Registered Trademark EN0B-0644GE51 R1109A
Copyright © 2009 Honeywell Inc. • All rights reserved
C7110A1010
ROOM AIR QUALITY SENSOR
SPECIFICATION DATA & INSTALLATION INSTRUCTIONS
GENERAL
The C7110A1010 Room Air Quality Sensor is suitable for
measuring air quality in rooms, offices, and production bays.
This mixed gas sensor can be used to control ventilation
plants. It detects unpleasant odors, tobacco smoke, and
vapors emitted by such materials as furniture, carpets, paint,
glue, etc. As proven in practice, this device detects those
substances typically present in air having a poor quality,
some of which may otherwise go undetected by room
occupants, themselves. This sensor has proven itself in
numerous applications over many years.
NOTE: The mixed gas sensor does not measure or indicate
the concentration of individual gases, and thus
cannot be used for the monitoring or control of
specific substances.
Models
order no. description output signal
C7110A1010 Room Air Quality Sensor 0...10 Vdc
FEATURES
Measurement of a variety of air quality factors
Output signal: 0...10 Vdc, indicated by yellow status
LED on front cover
Trimming potentiometer to adjust output signal
Easy installation and wiring connection
SPECIFICATION
Supply voltage 15...30 Vdc / 24 Vac (+/-20%)
Power consumption < 1 W
Output signal 0...10 Vdc (increases as air
quality worsens); adjustable via
trimming potentiometer
Min. impedance of load 5 kOhm (at output)
Weight /Dimensions approx. 125 g / see page 3
Electrical connection Screw terminal block for
conductors up to 1.5 mm²
Air Quality Sensor
Sensitivity/Linearity see Fig. 1 on page 2
Dynamic behavior see Fig. 6 on page 4
Ambient Limits
Transport/storage temp. -30...60 C (-22...+140 F
)
Operating temperature 0...+50 °C (+32...+122 °F)
Humidity 5...95%rh, non-condensing
Safety
Protection class III as per EN60730-1
Protection standard IP30 as per EN60529
Flame retardant Plastic ABS, V0 as per UL94
Question and Answer IconNeed help?

Do you have a question about the Honeywell C7110A1010 and is the answer not in the manual?

Honeywell C7110A1010 Specifications

General IconGeneral
Power Supply24 Vac
ColorWhite
Housing MaterialPlastic
MountingWall
Voltage24 VAC

Summary

GENERAL PRODUCT INFORMATION

GENERAL DESCRIPTION

Describes the C7110A1010 Room Air Quality Sensor's suitability for measuring air quality and controlling ventilation.

IMPORTANT NOTE ON GAS MEASUREMENT

Clarifies that the mixed gas sensor does not measure individual gas concentrations or specific substances.

SPECIFICATION DATA AND INSTALLATION

FEATURES

Highlights key features like air quality measurement, output signal, and ease of installation.

SPECIFICATIONS

Details technical specifications including supply voltage, power, output signal, and electrical connection.

AVAILABLE MODELS

Lists available models with order number, description, and output signal.

FUNCTION AND INSTALLATION PROCEDURES

OPERATIONAL FUNCTION

Explains the sensor's working principle and detected gases/particles, noting it's a broadband detector.

OPTIMAL POSITIONING GUIDELINES

Provides guidance on optimal placement to avoid falsifying measurements, avoiding sunlight and drafts.

MOUNTING INSTRUCTIONS

Details the steps for disassembling the cover and mounting the sensor unit onto a wall box or holes.

SIGNAL ADJUSTMENT AND WIRING

ADJUSTING THE OUTPUT OFFSET SIGNAL

Explains how to adjust the output signal using the trimming potentiometer on the sensor board for custom settings.

WIRING CONNECTION AND POTENTIOMETER FUNCTION

Details wiring connections and the function of the trimming potentiometer for signal adjustment, referencing status LED.

DYNAMIC BEHAVIOR AND FINAL ADJUSTMENT

EXAMPLE OF DYNAMIC BEHAVIOR

Illustrates sensor characteristics monitored in a sample room under different occupancy conditions.

FINAL ADJUSTMENT PROCEDURE

Outlines steps for connecting voltage, ensuring good air, and verifying the output signal after initial operation.