LYNX BACnet PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA
EN0Z-0959GE51 R0615
9
Table 4. Description of wiring terminals (CLLYUB6438S,
CLLYVB6436AS, and CLLYVB6438S)
TERMINAL LABEL CONNECTION
INPUT POWER & GROUND
1 24 VAC 24 VAC POWER
2
(
A
24 VAC COM 24 VAC POWER
3
(
A
EGND EARTH GROUND
4 SHLD SHIELD
5 SBUS 1 SYLK
6 SBUS 2 SYLK
NETWORK CONNECTIONS
7 BAC+ BACnet COMMUNICATIONS
8 BAC- BACnet COMMUNICATIONS
DIGITAL OUTPUTS
9 DO-1 DIGITAL OUTPUT
10 DO-2 DIGITAL OUTPUT
11 COM COMMON
12 DO-3 DIGITAL OUTPUT
13 DO-4 DIGITAL OUTPUT
14 COM COMMON
15 DO-5 DIGITAL OUTPUT
16 DO-6 DIGITAL OUTPUT
17 COM COMMON
18
(B
DO-7 DIGITAL OUTPUT
19
(B
DO-8 DIGITAL OUTPUT
20
(B
COM COMMON
ANALOG OUTPUTS
(C
21 AO-1 ANALOG OUTPUT
22 COM COMMON
23 AO-2 ANALOG OUTPUT
24 AO-3 ANALOG OUTPUT
25 COM COMMON
DIGITAL INPUTS
(D
26 DI-1 DIGITAL INPUT
27 DI-2 DIGITAL INPUT
28 COM COMMON
29 DI-3 DIGITAL INPUT
30 DI-4 DIGITAL INPUT
ATTACHED DEVICE(S) POWER
31 20 VDC 20 VDC POWER
UNIVERSAL INPUTS
32 UI-1* UNIVERSAL INPUT
33 COM COMMON
34 UI-2 UNIVERSAL INPUT
35 UI-3 UNIVERSAL INPUT
36 COM COMMON
37 UI-4 UNIVERSAL INPUT
38 UI-5 UNIVERSAL INPUT
39 COM COMMON
40 UI-6 UNIVERSAL INPUT
(A
A jumper should be installed between 24 VAC COM (term. 2) and EGND
(term. 3). Further, EGND (term. 3) should be connected to a verified earth
ground.
(B
In the case of the CLLYVL6436AS controller, only, terminals 18, 19, and 20
(DO-7, DO-8, and COM) are not present. The actuator is internally hardwired to
these terminals.
(C
Analog outputs may be configured as digital outputs and operate as follows:
FALSE (0%) -> 0 Vdc (0 mA), TRUE (100%) -> the max. 11 Vdc (22 mA)
(D
Digital inputs: open circuit = FALSE, closed circuit = TRUE
*UI-1 is selectable as a fast digital pulse meter.
Table 5. Description of wiring terminals (CLLYVB0000AS,
CLLYVB4022AS, and CLLYVB6436AS)
TERMINAL LABEL CONNECTION
INPUT POWER & GROUND
1 24 VAC 24 VAC POWER
2
(
A
24 VAC COM 24 VAC POWER
3
(
A
EGND EARTH GROUND
4 20VDC 20 VDC
5 SBUS 1 SYLK
6 SBUS 2 SYLK
NETWORK CONNECTIONS
7 BAC+ BACnet COMMUNICATIONS
8 BAC- BACnet COMMUNICATIONS
9 SHIELD SHIELD
DIGITAL OUTPUTS
10 DO-3 DIGITAL OUTPUT
11 COM COMMON
12 DO-4 DIGITAL OUTPUT
13 DO-2 DIGITAL OUTPUT
14 COM COMMON
15 DO-1 DIGITAL OUTPUT
ANALOG OUTPUTS
16 AO-2 ANALOG OUTPUT
17 COM COMMON
18 AO-1 ANALOG OUTPUT
UNIVERSAL INPUTS
19 UI-4 UNIVERSAL INPUT
20 COM COMMON
21 UI-3 UNIVERSAL INPUT
22 UI-2 UNIVERSAL INPUT
23 COM COMMON
24 UI-1
*
UNIVERSAL INPUT
(A
A jumper should be installed between 24 VAC COM (term. 2) and
EGND (term. 3). Further, EGND (term. 3) should be connected to a
verified earth ground.
*
UI-1 is selectable as a fast digital pulse meter.
MS/TP MAC Address DIP Switches
The MS/TP MAC address DIP switches are used to set the
unit's MAC address. Each LYNX controller on an MS/TP net-
work must have a unique MAC address in the range of 0-127
(address 0 should be avoided as it is the Honeywell factory
default MAC address for all MS/TP devices).
MS/TP Service Connector Pins
Local device MS/TP network connection is provided via the
molex connector pins.

Related product manuals