5
T8611G CHRONOTHERM
®
IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
A combination of key presses are required to use the
Installer Setup feature.
—To enter the Installer Setup, press and hold the
Information i key with the increase and
decrease keys until the first number is displayed.
All display segments appear for approximately three
seconds before the number is displayed.
See Fig. 9 and 10.
—To advance to the next Installer Setup, press the
Time key.
—To change a setting, use the increase or
decrease key.
—To scroll the Installer Setup numbers backwards,
press the Time key.
—To exit the Installer Setup, press Run Program.
Fig. 10. Display of Installer Setup
number and setting.
IMPORTANT
Only configurable numbers are shown on the device.
Example: If thermostat does not have a system key,
Installer Setup Number 12 will not be displayed.
Review Table 3 factory-settings and mark any
desired changes in the Actual Settings column.
When Installer Setup is complete, review the
settings to confirm that they match the system.
Table 3. Thermostat Installer Setup Options.
(Continued)
Fig. 9. Display of all the segments of the LCD.
Installer
Setup
Number
(Press
Time
key to
Factory-Setting
Other Choices
(Press or key to change)
Actual
Select
change)
Display Description Display Description
Setting
Not used 1 thru 4
Heating cycle
56Stage 2 3, 6 or 9
3—3 cph
6 (Not
used)
———
6—6 cph used for last stage of
heat pump systems
79Emergency heat 3, 6
or 9
9—9 cph used for electric
heat
Not used 8 thru 11
System setting
adjustment
12 1 Manual changeover 0 or 2 0—Auto changeover
2—Fixed auto changeover
Adaptive
Intelligent
Recovery™
control
13 0 Adaptive Intelligent
Recovery™ control is
activated (system
starts early so setpoint
is reached by start of
program period)
1 Conventional recovery (system
starts recovery at programmed
time)
Degree
temperature
display
14 0 Temperature is
displayed in °F
1 Temperature is displayed in °C
Not used 15
Clock format 16 0 12-hour clock format 1 24-hour clock format
Not used 17 and 18
Extended fan
operation in
heating
19 0 No extended fan
operation after the
call for heat ends
1 Fan operation is extended
90 seconds after the call for
heat ends.
M14618
INSTALLER SETUP
NUMBER DISPLAY
(COLUMN 2 OF TABLE 3)
FACTORY SETTING OR OTHER
CHOICE DISPLAY (COLUMN 3
OR 5 OF TABLE 3)
M14559
Aux Ht
Set Day/TimeSet Program
Mon
Wake Leave Return Sleep
OutdoorRoom
Filter
Wait
System
Fan
Em Heat
On
Auto
Off
Cool
Auto
AM
PM
Hold for
Heat
Cool
Repl Batt
Recovery
DST
Tue Wed Thu Fri Sat Sun
Days
Temporary Setting