MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS 
EN1Z-1035GE51 R0420  24   
WALL MODULES 
The CLCM1T,2T,4T,5T,6T111 and CLCMTR40x/TR42x Wall 
Modules can be used in conjunction with the controller to per-
form room temperature sensing, setpoint adjustment, fan 
speed manual override, and occupancy override. 
NOTE:  The CLCMTR42x Wall Module must be version 
1.00.3 or higher. 
Further, the LED of the CLCM4T,5T,6T111 and the LCD of 
the CLCMTR42x can be configured to provide information 
about: 
▪  any override of the controller by, e.g., pressing the 
"occupancy" button of the wall module or receipt by the 
controller of a BACnet MS/TP network command (see 
section "CLCM Configured to Display Info on Overrides" 
below); 
▪  the controller's effective occupancy mode (see section 
"CLCM Configured to Display Info on Occupancy" below). 
NOTE:  The intended use of the wall module's buttons must 
be configured using COACH NX. 
Table 12. Supported wall module functions 
 
temp. 
sensor 
A)
 
setpt. 
adjustment 
A)
 
bypass 
A)
 
fanspeed 
override 
A)
 
LED 
CLCM1T11N 
(T7460A1001) 
X  --  --  --  -- 
CLCM2T11N 
(T7460B1009) 
X  X  --  --  -- 
CLCM4T111 
(T7460C1007) 
X  X  X  --  X 
CLCM5T111 
(T7460E1002) 
X  X  X  auto-0-1 X 
CLCM6T111 
(T7460F1000) 
X  X  X  auto-0-
1-2-3 
X 
A) Requires one UI supporting NTC. 
 
NOTE:  The CLMERL8N has ten UIs, only two of which 
support NTC; this model is thus not suitable for the 
hardwiring of wall modules requiring three UIs 
supporting NTC. 
See also corresponding Technical Literature listed in Table 13 
on pg. 27. 
 
Configuration of Wall Module LED / LCD 
The LED of a CLCM4T,5T,6T111 Wall Module can be con-
figured (using COACH NX) to provide information about, e.g., 
overrides or effective occupancy modes. The LCD of the 
CLCMTR42x can likewise be configured to display such 
information. 
 
CLCM Configured to Display Info on Overrides 
The LED of a CLCM4T,5T,6T111 Wall Module connected to 
the controller can be configured to indicate if an override has 
been activated because either the wall module's override 
button has been pressed or the controller has received a 
BACnet MS/TP network command. Specifically, the following 
modes are supported: 
▪  NO OVERRIDE: If the wall module's LED is OFF, then no 
override is currently in effect. 
▪  OVERRIDE OCCUPANCY: If the wall module's LED is 
ON continuously, then the wall module's override button 
or a BACnet MS/TP network command has placed the 
controller into the "occupied" or "override" mode (but if the 
override button is again pushed or if a cancellation net-
work command is received or if the override time expires, 
the controller will return to its scheduled occupancy mode, 
and the wall module's LED will behave accordingly). 
▪  OVERRIDE HOLIDAY: If the wall module's LED flashes 2 
sec OFF and 1 sec ON, then the controller has received a 
network command and been placed in the "holiday" mode. 
▪  OVERRIDE UNOCCUPIED: If the wall module's LED 
flashes once per sec, then the wall module's override 
button or a network command has placed the controller 
into the "unoccupied" mode (however, if the override 
button is again pushed or if a cancellation BACnet MS/TP 
network command is received, the controller will return to 
its scheduled occupancy mode, and the wall module's 
LED will behave accordingly). 
▪  If the wall module's LED flashes twice per sec, then a 
BACnet MS/TP network command has placed the con-
troller into either the "standby" or the "occupied" mode. 
 
CLCM Configured to Display Info on Occupancy 
The LED of a CLCM4T,5T,6T111 Wall Module connected to 
the controller can also be configured to indicate the con-
troller's effective occupancy mode. Specifically, the following 
modes are supported: 
▪  UNOCCUPIED: If the wall module's LED is OFF, then the 
controller is in the "unoccupied" mode. 
▪  STANDBY: If the wall module's LED flashes once per sec, 
then the controller has received a network command and 
been placed in the "standby" mode. 
▪  OCCUPIED: If the wall module's LED is ON, then the con-
troller is in the "occupied" mode. 
▪  BYPASS: If the wall module's LED is ON continuously, 
then the controller has received a network command and 
been placed in the "bypass" mode. 
▪  HOLIDAY: If the wall module's LED is OFF, then the con-
troller has received a network command and been placed 
in the "holiday" mode. 
 
LCD of a TR42x Configured to Display Info on Occupancy 
The LCD of a CLCMTR42x connected to the controller can be 
configured to display various texts and symbols to indicate 
the effective occupancy mode of the controller. See the 
following sections "Unoccupied Mode," "Standby Mode," and 