Differential Pressure Switches DPS Series
FOR AIR CONDITIONING / VENTILATION, USER-ADJUSTABLE
PRODUCT DATA AND INSTALLATION INSTRUCTIONS
TECHNICAL SPECIFICATIONS
Max. operating pressure 10 kPa
Pressure media air, non-flammable gases, and
non-aggressive gases
Pressure connections two plastic tubes, outside
diameter: 6.0 mm
Switching capacity 1.5 A, (0.4) /250 Vac
Electrical connections AMP connectors, 6.3 x 0.8,
DIN 46244 or screw terminals
Conduit entry M20x1.5
Protection class IP 54
Mounting lugs integrated in bottom housing
(alternative: mounting angles)
Medium/ambient temp. -20...+85 °C
Storage temperature -40...+85 °C
Membrane material silicone
APPLICATION
Differential pressure switches e.g. for monitoring filter, fan,
fire damper, or air flow status of air handling systems.
BENEFITS
Switching-point easily adjustable with scale in Pascal;
Direction of M20x1.5 conduit entry can be rotated in steps
of 120°;
Only one screw needed for housing cover.
APPROVALS
CE according to 2014/35/EU.
EC Gas Appliance Directive 2009/142/EC according to
DIN EN 1854: 2010.
ROHS 2011/65/EC.
(Eurasian Conformity)
e
CONTENTS OF DELIVERY
The delivery includes (in the case of individual packages) the
following parts:
1 DPS Differential Pressure Switch
1 Data Sheet with installation information
1 DPSA duct kit, consisting of:
- 2 m of silicone hosing
- 2 joining pipes with four screws
- 2 self-tapping screws for mounting the housing
- 3 terminal screws for electrical installation
Bulk packages available, upon request.
OPERATING RANGES
type
adjustment
range for upper
trip pressure*
switching
difference
(hysteresis)
tolerance at
adjusted
switch-point
DPS 200 20...200 (Pa) 10 (Pa) ±20%
DPS 400 40...400 (Pa) 20 (Pa)
±15%
DPS 500 50...500 (Pa) 20 (Pa)
DPS
1000
200...1000 (Pa) 100 (Pa)
DPS
2500
500...2500 (Pa) 150 (Pa)
*The trip pressure refers to vertical mounting. In case of
horizontal mounting (with the cover pointing upwards), the
range values increase by 20 Pa.
DIMENSIONS
See "Mounting/Einbau/Montage" on page 4.
ACCESSORIES / DELIVERY OPTION
DPST: Set of three screw terminals
DPSJ: Joining pipe (part of DPSA duct kit)
DPS…B in bulk pack (45 pc. per box), without
accessories, but with 1 set of Mounting Instructions
Question and Answer IconNeed help?

Do you have a question about the Honeywell DPS 200 and is the answer not in the manual?

Honeywell DPS 200 Specifications

General IconGeneral
BrandHoneywell
ModelDPS 200
CategorySwitch
LanguageEnglish

Summary

Product Data and Installation Instructions

Technical Specifications

Details on pressure, media, capacity, connections, protection, and temperature ratings.

Application

Describes typical uses of differential pressure switches in air handling systems.

Operating Ranges

Covers adjustment ranges and hysteresis for various DPS switch types.

Dimensions

Directs users to page 4 for detailed mounting dimensions.

Accessories and Delivery Options

Lists available accessories and package contents for the DPS series.

Mounting and Installation

Mounting Instructions

Step-by-step diagrams and notes for installing the DPS series pressure switch.

Important Notes for Installation

Crucial warnings regarding installation orientation and transport protection removal.

Related product manuals