APPLICATION
The Honeywell EC/RM7823A Relay Module is a
microprocessor based flame detector relay that can be fitted
with any 7800 SERIES Flame Amplifier to provide relay action
from one dpdt relay when flame is or is not present. The
EC/RM7823A system consists of a relay module, wiring
subbase and flame amplifier. Options include keyboard
display module (KDM), personal computer interface, Data
ControlBus Module™, remote display mounting and
Combustion System Manager™ Software.
Functions provided by the EC/RM7823A include flame
monitoring, self-diagnostics and troubleshooting.The
EC/RM7823A is a solid state replacement for the R7023B,C
Flame Detector Relays.
The EC7823/RM7823 is a flame detector relay only. A
switchable primary control must be used to provide safe-start
check, safety lockout, load switching and other functions
required in Flame Safeguard systems.
This document provides installation and static checkout
instructions. Other applicable publications are:
SPECIFICATIONS
Electrical Ratings, see Table 3:
Voltage and Frequency:
EC7823A: 220-240 Vac +10%/-15%, 50/60 Hz ±10%.
RM7823A: 120 Vac, +10%/-15%, 50/60 Hz, ± 10%.
Power Dissipation:
10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing: Total Connected Load: 15A, type SC, Fast Blow, or
equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to +60°C).
Storage: -40°F to 150°F (-40°C to +66°C).
Humidity: 85% relative humidity continuous, noncondensing.
Vibration: 0.5G environment.
Approvals:
RM7823A:
Underwriters Laboratories Inc. Listed: File No. MP268,
Guide No. MCCZ.
Canadian Standards Association Certified: LR9S329-3.
Factory Mutual Approved: Report No. J.I.1V9A0.AF.
IRI Acceptable.
Federal Communications Commission:
Part 15, Class B, Emissions.
EC7823A:
Factory Mutual Approved: Report No. J.I.1V9A0.AF.
IRI Acceptable.
Federal Communications Commission:
Part 15, Class B, Emissions.
Form
Number Description
63-2278 Q7700A Network Interface Unit Product Data
65-0084 Q7800A,B 22-Terminal Wiring Subbase Product
Data
65-0090 S7800A Keyboard Display Module Product Data.
65-0091 S7810A Data ControlBus Module™ Product Data
65-0095 S7820 Remote Reset Module Product Data
65-0097 221729C Dust Cover Packing Sheet
65-0109 R7824, R7847, R7848, R7849, R7851, R7861,
R7886 Flame Amplifiers for the 7800 SERIES
Product Data
65-0131 221818A Extension Cable Assembly Product Data
65-0229 7800 SERIES Relay Modules Checkout and Test
Question and Answer IconNeed help?

Do you have a question about the Honeywell EC7823A and is the answer not in the manual?

Honeywell EC7823A Specifications

General IconGeneral
TypeControl Unit
Frequency50/60 Hz
Humidity Range10% to 90% RH (non-condensing)
Communication ProtocolModbus RTU
Weight0.5 kg
ApprovalsCE, UL
Temperature Range-40°F to +140°F (-40°C to +60°C)
Operating Temperature-40°F to +140°F (-40°C to +60°C)

Summary

Application Overview

Technical Specifications

Electrical Ratings

Details on voltage, frequency, and power dissipation.

Environmental Ratings

Operating and storage temperature, humidity, and vibration limits.

Product Approvals

List of certifications and acceptances by various bodies.

Installation Instructions

General Installation Precautions

Key steps and warnings before starting installation.

Location and Environmental Factors

Guidance on selecting location and considering environmental factors.

Mounting the Q7800 Wiring Subbase

Instructions for mounting the wiring subbase.

Wiring the Subbase

Important warnings and guidance for wiring the subbase.

Final Wiring Check

Mounting the EC/RM7823A Relay Module

Mounting Other System Components

Operation and Status Indicators

Sequence of Operation

Describes the operating sequences and LED indications.

Static Checkout Procedure

Tests to perform before installing the relay module.

General Static Checkout Instructions

Related product manuals