Honeywell Electrode Steam - Interpreting LED Status Lights

Honeywell Electrode Steam
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EVERYDAY
OPERATION
The HM700 user interface includes 2 LEDs that provide information about the humidier status.
Yellow and Green LED Flashing.
Indicates there is no request for humidity.
Yellow LED Flashing.
Fault detected, humidier has stopped operating.
Green LED Flashing.
Indicates the humidier is powered, but the control
equipment (stat, air proving, fan, etc.) has interrupted
the call for humidity.
Yellow LED On.
Indicates that water level is high. When the yellow LED
is steady on (not ashing) it indicates that the high
water sensor has interrupted lling of the cylinder. The
LED is on for information only and unless it persists
for an extended period of time, it does not require any
action.
Green LED On.
Indicates steam is being produced.
What do the lights tell me?