EasyManua.ls Logo

Honeywell GENT S4 - Testing Beam Sensor Pairs; FIRE Test Procedure with Test Card; FAULT Test Procedure with Card

Honeywell GENT S4
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Test
How to test a beam sensor pair
After all the beam sensor pairs are fully commissioned use the appropriate test card (S4-34741-50) to
obscure the beam to simulate a FIRE or FAULT condition.
If a Test Keyswitch unit is connected to a 'beam transmitter' of a beam sensor pair then, if appropriate,
operate the switch to test the beam sensor pair. A test using a Test Keyswitch is not applicable for S4 beam
sensors converted to be backward compatible.
STATE FIRE test using a test card FAULT test using a card
0 Use the 50% obscuration Test card in the beam path Use a piece of cardboard to block the
beam path for 40 seconds
1 Use the 50% obscuration Test card in the beam path
Use cardboard to block the beam path for 40 seconds
N/A
2 Use the 25% obscuration test card in the beam path Use a piece of cardboard to block the
beam path for 40 seconds
3 Use the 25% obscuration test card in the beam path
Use a cardboard to block the beam path for 40
seconds
N/A
Commissioning information S4 Beam Sensor & brackets
14 4188-968 issue 4_Part 2_07-12_S4 mains interface
Test Card
Adhesive tape
Smoke pole
Floor level
Transmitter
Flashing
Flashing
A fire indication is given at the
and not at a ‘Beam transmitter’.
Also a fire indication is given at the panel.
Beam
receiver only
Transmitter
Receiver
Beam

Related product manuals