INSTALLATION INSTRUCTIONS
33-00360EF-05
HPZC10*
HONEYWELL HYDRONIC PRO
ZONE VALVE CONTROL PANEL
WHAT'S IN THE BOX?
Hydronic Zone Panel
Mounting Hardware (3 Screws and 3 Wall Anchors)
•2, 2-Amp Fuses
Install Manuals (English & French)
CAUTION
1. Disconnect power supply before beginning
installation to prevent electrical shock or
equipment damage.
2. Use copper conductors only.
3. Use only NEC Class 1 wire for all line voltage
wiring connections. Class 1 wires must be
rated for at least 167 °F (75 °C).
4. For installation by professionals only.
PANEL SPECIFICATIONS
Table 1.
1
Each transformer is protected with a 2 Amp replaceable fuse.
2
Transformers have a Class 2 output and are rated for 24V, 40VA at 25 °C. It is up to the installer to ensure that the 40VA
transformer rating is not exceeded.
3
All circulator relay connections are rated for 5A full load and 30A locked rotor (1/6 to 1/2HP depending on technology)
at 120VAC. Check circulator plate ratings to ensure full load current is not exceeded.
Model Zones
Transformers
1
Input Power
Electrical Rating for
Main Burner, End
Switch Burner, and
Zones
2
Electrical Rating for
Pump End Switch and
Priority Pump
3
Priority
Zone
Control
Type 1 Enclosure
Width Height Depth
HPZC103 3 (1) 24V 40VA 120VAC, 60Hz, 1 24V, 1 A 120 VAC
5FLA, 30LRA
Yes 10-1/4" 7-1/2" 2-1/8"
HPZC104 4 (1) 24V 40VA 120VAC, 60Hz, 1 24V, 1 A 120 VAC
5FLA, 30LRA
Yes 10-1/4" 7-1/2” 2-1/8"
HPZC105 5 (2) 24V 40VA 120VAC, 60Hz, 1 24V, 1 A 120 VAC
5FLA, 30LRA
Yes 11-3/4" 7-1/2" 2-1/8"
HPZC106 6 (2) 24V 40VA 120VAC, 60Hz, 1 24V, 1 A 120 VAC
5FLA, 30LRA
Yes 11-3/4" 7-1/2" 2-1/8"
Question and Answer IconNeed help?

Do you have a question about the Honeywell HPZC104 and is the answer not in the manual?

Honeywell HPZC104 Specifications

General IconGeneral
BrandHoneywell
ModelHPZC104
CategoryControl Panel
LanguageEnglish

Summary

Installation Instructions

Panel Specifications

Mounting

Hang Hole Flow

Describes mounting the panel using a wall-mounted screw and leveling.

Din Rail Flow

Details mounting the panel on a DIN rail.

Wiring and Setup

Standard Wiring Layout

Explains the standard wiring configurations for 6-zone and 4-zone panels.

Priority Override

Circulator Pump Operation

Zone Valve

Boiler Controls

NO PRIORITY ZONE OR PRIORITY END SWITCH

Describes boiler relay control logic without priority zone or priority end switch.

PRIORITY ZONE, NO PRIORITY END SWITCH

Details control logic when a priority zone is active but no priority end switch is used.

PRIORITY ZONE, PRIORITY END SWITCH

Explains control logic with both priority zone and priority end switch active.

Troubleshooting

Valve Fuse Protection

Explains how the resettable fuses protect zone valve outputs.

Status Label

Regulatory Information

5-Year Limited Warranty