Page 1 - Set RID, PAN ID and RF Channel in E528.4G and E527.4G
Set Room ID, PAN ID and RF Channel in INNCOM
E528.4G and E527.4G Thermostats
Enter Service Mode
Service mode is accessed by executing the following button sequence:
1. Press and hold F/C.
2. Press and release OFF/AUTO.
3. Press and release DISPLAY.
4. Release F/C.
The LCD display will now read “rid” confirming that you are in service mode.
Set Room ID
A unique 5-digit Room ID is required in each INNCOM thermostat.
Enter Service Mode and follow the procedure below to set the Room ID of the thermostat.
1. Scroll to rId
2. Press DISPLAY button and the current Room ID will scroll on the display.
3. After the Room ID scrolls, the highest digit of the Room ID will be displayed with the
HI fan indicator. Use the up or down arrow buttons to change the value and press
OFF/AUTO.
4. The next 2 digits of the Room ID are now displayed along with the MED fan indicator.
Use the up or down arrow buttons to change the value and press OFF/AUTO.
5. The last 2 digits of the Room ID are now displayed along with the LO fan indicator
Use the up or down arrow buttons to change the value and press OFF/AUTO.
6. Press the DISPLAY button to store the new Room ID. The new Room ID will scroll
across the display.
Example of RID for Room 515 (00515)