EasyManuals Logo

Honeywell LCBS User Manual

Honeywell LCBS
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
LCBS CONNECT SOLUTION
37 31-00118EFS—01
9. Single Stage Heat Pump with Economizer Differential Enthalpy
Changeover and Temperature Limit
MCR36716
BUILDING NAME
CVAHU RTU NAME
DATE
COOL 1
AUX HEAT
FAN
C7400S SYLK OUTSIDE
AIR ENTHALPY SENSOR
C7400S SYLK RETURN
AIR ENTHALPY SENSOR
REV VALVE O
SINGLE STAGE HEAT PUMP ECONOMIZER DIFFERENTIAL ENTHALPY
SYLK BUS
24 VAC
CONTROLLER
POWER
LCBS
CONTROLLER
WALL
MODULE
C7250A MIXED AIR SENSOR
C7250A DISCHARGE AIR SENSOR
C7400S RETURN AIR ENTHALPY SENSOR
M7215A ECONOMIZER ACTUATOR
AT40 TRANSFORMER(S)
THIS APPLICATION PROVIDES AUTOMATIC CONTROL OF AN AIR TO AIR HEAT PUMP AND INTEGRATED
ECONOMIZER WITH DIFFERENTIAL ENTHALPY CONTROL AND HIGH TEMPERATURE LIMIT (SEE APP
GUIDE FOR DETAILED SEQUENCE). REVERSING VALVE IS ENERGIZED IN COOLING MODE AND INITIATES
COOLING CYCLE BASED ON 24 VAC SUPPLIED CONFIGURER HAS THE OPTION TO RUN THE HEAT PUMP
IN A “COMFORT MODE” OR “SAVINGS MODE.” THE NORMAL MODE WILL OPERATE THE HEAT PUMP
AUXILIARY HEAT BASED ON CONFIGURER SELECTED HEATING SETPOINT. IN THE “SAVINGS MODE”
THE HEATING SETPOINT IS DEPRESSED SO THAT ELECTRIC, AUXILIARY HEAT OPERATES LESS
FREQUENTLY. REFER TO APPLICATION GUIDE TO REFERENCE SETUP, SETBACK OPERATION AS WELL
AS ADAPTIVE INTELLIGENT RECOVERY OPERATION. SYSTEM SUPPLY FAN AUTOMATICALLY OPERATES
IN A CONTINUOUS MANNER DURING OCCUPIED PERIODS AND CYCLES ON A CALL FOR COOLING
DURING UNOCCUIPED PERIODS TO MEET THE NEED OF PREVAILING BUILDING CODES.
LCBS CONNECT – INFORMATION
OS#
DESCRIPTION
YCRL6438SR LCBS CONTROLLER (WITH WALL MODULE)
LCBS CONNECT – COMPONENTS SHOWN
C7400S OUTDOOR AIR ENTHALPY SENSOR
C7250A
MA SENSOR
C7250A
DA SENSOR
C7250A
OA SENSOR
ACTUATOR
24 VAC
POWER
M7215A
ECONOMIZER
ACTUATOR
1 2 3 4 5 6 78
9
10 11 12 13 14 15 16 17 18 19 20
21 22 23
24 25
26
27 28
29 30 31 32 33 34 35 36 37 38 39 40
24VAC
COM
24VDC
24VAC
R
W1
W2
W3 OB G-L
Y1
Y2
Y3 G-L
RH
RC
COM AUX
DO1 AUX
G
UI-1
DI-2
DI-3
UI-4
UI-5
UI-6
UI-2
UI-3
COM
COM
COM
DI-4
DI-1
COM
AO-3
AO-1
COM
A0-2
COM
NET-1
NET-2
S-BUS
S-BUS
SHIELD
EGND
LCBS
CONTROLLER
HVAC SYSTEM
24 VAC POWER
EXISTING
TRANSFORMER

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell LCBS and is the answer not in the manual?

Honeywell LCBS Specifications

General IconGeneral
BrandHoneywell
ModelLCBS
CategoryController
LanguageEnglish

Related product manuals