SYSTEM ENGINEERING GUIDE
63-2484—03
Solid State Economizer System
(CONSISTING OF: C7046C DISCHARGE AIR SENSOR OR C7150B MIXED AIR SENSOR, C7400 SOLID STATE ENTHALPY
SENSOR OR C7660 SOLID STATE TEMPERATURE SENSOR, M7415, M7215 OR M8405 DAMPER ACTUATORS OR MODU-
LATING DIRECT COUPLED ACTUATORS (MS7503 or MS7505) T6031H THERMOSTAT AND W7459 OR W7212 SOLID
STATE ECONOMIZER LOGIC MODULE)
APPLICATION
The Solid State Economizer System provides an economical
method of providing cooling air by incorporating outdoor air in
the first stage of cooling in heating, ventilating and air
conditioning (HVAC) systems. The Solid State Economizer
System consists of the C7046C Discharge Air Sensor or
C7150B Mixed Air Sensor, C7400 Solid State Enthalpy
Sensor or C7660 Solid State Temperature Sensor, M7215,
M7415 or M8405 Damper Actuators or Modulating Direct
Coupled Actuators (MS7503 or MS7505), T6031H Thermostat
and W7212A,C or W7459A,C Solid State Economizer Logic
Module.
FEATURES
C7046C Discharge Air Sensors have probe lengths of 8 in.
(203 mm) and nominal sensor resistance of 3000 ohms at
77°F (25°C).
No setting or calibration required.
Solid state components not affected by dust or dirt.
Fast reacting.
Rugged aluminum insertion probe.
C7150B Mixed Air Sensor is used with the W7212/W7459
Economizer Module to sense mixed or discharged air in roof-
top packaged air conditioning equipment.
No setting or calibration required.
C7400 Solid State Enthalpy Sensor and C7660 Solid State
Temperature Sensors are used with the W7212/W7459 Solid
State Economizer Logic Module to sense outdoor and return
air enthalpy or temperature.
C7400 senses and combines temperature and humidity
(enthalpy) of outdoor air (heat index).
C7660 senses temperature only and can only be used
in single referential control. Use C7400 enthalpy for
differential control.
When enthalpy/temperature of outdoor air increases,
the outdoor air damper closes to a preset minimum
position.
When enthalpy/temperature of outdoor air is low, the
outdoor air damper opens to reduce the building
cooling load.
C7150B
M7215/M7415/
M8405
C7046C
W7459A,C
C7400A/C7660
W7212A,C
T6031H

Other manuals for Honeywell M7415

Questions and Answers:

Honeywell M7415 Specifications

General IconGeneral
Input Voltage24 VAC
ApplicationHVAC Control
Control Signal2-10 VDC or 4-20 mA
Operating Temperature Range-40 to 150°F
Relay Contact Rating5A

Summary

Solid State Economizer System

FEATURES

Overview of system components and their capabilities.

APPLICATION

Explains the system's purpose and benefits in HVAC.

Component Descriptions: Actuators, Thermostat, Logic Modules

Details on M7415, M8405 actuators, T6031H thermostat, W7459/W7212 modules.

Sensor Descriptions

Details on C7046, C7150B, C7400, C7660 sensors.

SPECIFICATIONS

Sensor Specifications

Technical details for C7046, C7150B, C7400, C7660 sensors.

Actuator and Motor Specifications

Specs for M7415, M8405, M7215 damper actuators/motors.

Logic Module and Thermostat Specifications

Specs for W7459, W7212 logic modules & T6031H thermostat.

INSTALLATION

Damper Actuator Installation

Procedures for installing M7215, M7415, M8405 actuators.

Sensor Mounting

Instructions for mounting C7046C Discharge Air Sensor.

Logic Module Mounting

Mounting instructions for W7459 and W7212 logic modules.

SEQUENCE OF OPERATION

Economizer Sequence of Operation

Step-by-step explanation of the economizer's operating sequence.

W7212 Operation Modes

How the W7212 module operates for cooling and occupancy.

Troubleshooting

Outdoor Enthalpy Above Setpoint Issues

Resolving problems when outdoor enthalpy is above setpoint.

Outdoor Enthalpy Below Setpoint Issues

Resolving problems when outdoor enthalpy is below setpoint.