MINIPEEPER
®
 ULTRAVIOLET FLAME DETECTORS
60-2026-16 4
Fig. 4. Installation dimensions of C7927A1016 in inches (mm).
INSTALLATION
When Installing This Product...
1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazardous 
condition.
2. Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application.
3. Installer must be a trained, experienced, flame safeguard 
control technician.
4. After installation is complete, check out product opera-
tion as provided in these instructions.
Disconnect power supply before beginning installation to 
prevent electrical shock and equipment damage. All wiring 
must comply with applicable electrical codes, ordinances 
and regulations. Use NEC Class 1 wiring.
NOTICE
Per industry standards, a conduit seal, or a cable type that is 
sealed, is required to be installed in a device that can result in 
a flammable gas or flammable liquid flow through a conduit or 
cable to an electrical ignition source in the event of a seal 
leakage or diaphragm failure.
IMPORTANT
The C7027, C7035, and C7044 ultraviolet radiation 
sensing tubes have a life expectancy of 40,000 hours 
of continuous use within the flame detector's specified 
ambient temperature and voltage ratings. When an 
ultraviolet radiation sensing tube wears out, the UV 
sensor will fail to properly discriminate between flame 
conditions.
The C7027A, C7035A, C7044A and C7927 Flame 
Detectors should only be used on burners that cycle 
on/off or, in the absence of cycling, are periodically 
checked for proper operation following the application 
instructions provided by the equipment manufacturer.
Follow recommended industry standards for the fre-
quency of sensor checks, either through cycling 
(employing safe-start check methods) or periodic 
maintenance. If uncertain, industry guidelines sug-
gest one burner cycle in a 24-hour period.
Consult the equipment manufacturer or the governing 
standard for recommendations about frequency of 
checks.
Controls incorporating safe-start checks, and sensors 
and controls employing constant check means are 
available from Honeywell. See your Honeywell repre-
sentative for specific information.
3-7/8 (98)
3-3/8 (86)
8 FOOT 
(2.44 METER)
LEADWIRES (2)
1
(25)
C7927A1016
M24713A
COLLAR WITH 1/2-14 NPSM 
INTERNAL THREADS
SPUD CONNECTOR (1/2-14
NPSM INTERNAL THREADS)