MINIPEEPER
®
 ULTRAVIOLET FLAME DETECTORS
9 60-2026-16
3. Avoid installation considerations that can influence 
detector operation and maximum lead wire length, such 
as:
a. Moisture.
b. Ignition interference.
c. High resistance connections—poor grounds.
d. Lead wire capacitance.
e. Voltage fluctuations.
f. Induced line transients.
g. Floating grounds—ground at some voltage above 
earth ground.
h. No G wire—burner used as ground.
i. Detector output less than maximum attainable for the 
installation (inadequate sighting.
IMPORTANT:
 Do not run the flame detector wiring in the same con-
duit with high voltage ignition transformer wires.
Connecting Detectors In Parallel
(C7927 Can Not be Used in Parallel)
For a flame that is difficult to sight, using two flame detectors 
connected in parallel will reduce the occurrence of nuisance 
shutdowns. If only one of the parallel detectors loses the flame 
signal, the other will continue to indicate the presence 
of the flame and keep the burner in operation.
When the flame detectors are connected in parallel, the low 
level background signals are additive. Therefore, no more than 
two C7027A, C7035A, or C7044A Flame Detectors should be 
paralleled. Furthermore, the background signal increases as 
temperature decreases. Because of this, the minimum ambient 
operating temperature must be increased when the C7027A, 
C7035A or C7044A Flame Detectors are paralleled. (C7927 
can not be used in parallel.)
When using detectors rated for a minimum of 0°F (-18°C), limit 
the minimum ambient temperature at the detectors to 32°F 
(0°C). When using detectors rated for a minimum of 
 -40°F (-40°C), limit the minimum ambient temperature at the 
detectors to -10°F (-23°C).
Connect the blue lead wires of both detectors to the F terminal 
of the wiring subbase or terminal strip, and the white lead wires 
of both detectors to the G terminal, as shown in Fig. 9.
Earth Ground
The detector and the flame safeguard control must be 
connected to earth ground. A convenient method of 
accomplishing this is to connect the detector to the flame 
safeguard control with a flexible conduit, or ensure a good 
ground connection at the mounting bracket.
 
Fig. 9. Wiring C7027A, C7035A, and
 C7044A flame detectors in parallel.
ADJUSTMENTS AND 
CHECKOUT
Before welding the C7027A, C7927A or C7035A sight pipe 
in its final location, or before tightening the C7044A clamp 
screw, complete both the adjustments and checkout tests that 
follow and any required by the burner manufacturer.
UV Sensor Tube Test
NOTE: For initial burner light off, consult the burner manufac-
turer instructions or the instructions
for the flame safeguard control.
During the initial burner light off, make sure the flame 
safeguard control starts (i.e., the load relay, usually 1K, pulls 
in). If it does not start, visually check the sensing tube in the 
C7027A, C7035A, or C7044A flame detector. If the tube 
continues to glow when no flame is present, replace the 
sensing tube (C7035A), or replace the detector (C7027A or 
C7044A).
Adjust Detector Sighting Position
With the flame detector installed and burners running, adjust 
the position of the flame detector for optimum flame signal. The 
flame signal will be read in microamps or voltage (Vdc) 
depending on the Honeywell flame safeguard combustion 
control used.
Most existing Honeywell flame safeguard controls incorporate 
a flame current jack on the flame amplifier or on the control 
itself. The flame signal can be measured with a volt-ohmmeter 
such as the Honeywell W136A. To measure the flame current 
(signal), use a cable connector (part number 196146, included 
with the W136A) in conjunction with the meter. With the 
W136A (or equivalent) positioned at the zero to 25 
microampere scale, make connections from the meter probes 
to the two ends of the cable connector plug (red to red, black to 
black). Make these connections before inserting the plug end 
of the connector plug into the flame jack of the control 
or control amplifier (see Fig. 10). Read the flame signal in 
microamperes directly from the W136A meter. Refer to 
Table 1 for the minimum acceptable flame currents.
Fig. 10. Measuring microamp flame signal.
M3018A
F
WIRING SUBBASE
OR 
TERMINAL STRIP 
OPTIONAL
SECOND
DETECTOR
UV DETECTOR
UV DETECTOR
BLUE
BLUE
WHITE
WHITE
G
W136A VOLT-
OHMMETER
W136A SELECTOR
SWITCH
196146 METER
CONNECTOR
PLUG
PLUG
FLAME SIGNAL
METER JACK
PLUG-IN FLAME
SIGNAL AMPLIFIER
RED CONNECTOR
BLACK CONNECTOR
BLACK (-) METER LEAD
RED (+)
METER
LEAD
M6532B