MINIPEEPER
®
 ULTRAVIOLET FLAME DETECTORS
60-2026-16 6
Mounting a C7027A, C7927 or C7035A
Locate the Sight Pipe
The location of the sight pipe is the most critical part of the 
installation. A black iron pipe is recommended. Do not use a 
stainless steel or galvanized pipe because its internal surface 
blackens with use as deposits from the combustion chamber 
settle on it. Initially, its shiny internal surface reflects ultraviolet 
radiation, which could result in a satisfactory flame signal, even 
though the pipe may be improperly located. As it blackens, less 
ultraviolet radiation is reflected and the flame signal may 
become marginal.
Under optimum sighting conditions, the C7027A, C7927 and 
C7035A Flame Detectors can detect most common gas and oil 
combustion flames at a distance of six feet. The critical factors 
in determining the flame-detector distance separation are the 
optimized flame signal (current or voltage) and the flame 
detector temperature. Other factors may be influential and are 
associated with the specific installation. For minimum flame 
signals, see Table 1 and for ambient operating temperatures, 
refer to Specifications, page 2.
Use 1/2 in. pipe for a C7027 or C7927, and 1 in. pipe for 
a C7035. Since no two situations are likely to be the same, 
length and sighting angle of the pipe must be determined at the 
time and place of installation. Generally, it is desirable 
to have the sight pipe tilting downward to prevent soot or dirt 
buildup.
If a C7027A or C7927A is to be used for a blast tube 
installation, its location should be determined by the burner 
manufacturer; contact the manufacturer before making any 
modifications to the installation.
In locations where water is usually sprayed on the body of the 
detector, use a C7035A. Internal threads in its base permit the 
use of waterproof flexible conduit for this type of application.
Prepare Hole In Wall Of Combustion Chamber
Cut a hole of the proper diameter for the sight pipe in the wall 
of the combustion chamber at the selected location. Flare the 
hole to leave room for small adjustments of the sighting angle. 
The taper of the hole should be about 1 in. for every 3 in. 
(25 mm for every 76 mm) of wall thickness.
Mounting The Sight Pipe (Fig. 5)
Thread one end of the pipe to fit the mounting collar on the 
detector. Cut the pipe to the desired length (as short as 
practicable), and at an angle so it fits flush with the wall of the 
combustion chamber. Tack-weld the pipe to the wall in a trial 
position. Do not permanently weld the sight pipe in place until 
after completing the Adjustments and Checkout beginning on 
page 9.
NOTE:  If you use a swivel mount (part no. 118367A) and you 
are positive about the location and sighting angle, you 
can permanently weld the pipe.
Fig. 5. Mounting sight pipe.
Sight Pipe Ventilation
It may be necessary to ventilate the sight pipe to cool the flame 
detector or to clear the sight pipe of UV radiation absorbing 
substances such as smoke, excessive moisture or, in some 
instances, unburned fuel.
For a negative pressure combustion chamber, drilling a few 
holes in the section of the sight pipe outside of the combustion 
chamber will allow air at atmospheric pressure to flow through 
the sight pipe into the chamber. A perforated pipe nipple 
between the sight pipe and the detector can also be used 
(see Fig. 6).
For a positive pressure combustion chamber, connect a supply 
of pressurized air from the burner blower through the sight pipe 
into the chamber. The supply air pressure must be greater than 
the chamber pressure.
FLARED HOLE
REFRACTORY
M3019C
TEMPORARY
TACK WELD
BLACK IRON
SIGHT PIPE
BOILER
PLATE