TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
13 63-2675—01
0310 Deadband 3°F
(2°C)
2 (1.5)—2°F (1.5°C)
3 (2.0)—3°F (2.0°C)
4 (2.5)—4°F (2.5°C)
5 (3.0)—5°F (3.0°C)
6 (3.5)—6°F (3.5°C)
7 (4.0)—7°F (4.0°C)
8 (4.5)—8°F (4.5°C)
9 (5.0)—9°F (5.0°C)
Only shown if Automatic Changeover selected (ISU
0300).
0320 Temperature
Indication Scale
0 0—°F
1—°C
0330 Daylight Saving 1 0—Disabled
1—Enabled (US)
0340 Remote Temp
Sensor/Remote
Setback/
Changeover Input
0 0—None
1—Remote 10K Indoor
2—Remote 20K Indoor
3—Changeover 2 pipe Fan Coil
modes only
4—Changeover 2 pipe Fan Coil
modes only
Only shown on models that offer remote sensing.
NO input (default mode is Heat)
NO input (default mode is Cool)
0340
(Non-
program
mable)
Remote Temp
Sensor/Remote
Setback/
Changeover Input
0 0—None
1—Remote 10K Indoor
2—Remote 20K Indoor
3—Changeover 2 pipe Fan Coil
modes only
4—Changeover 2 pipe Fan Coil
modes only
5—Remote Setback
6—Remote Setback
Only shown on models that offer remote sensing.
NO input (default mode is Heat)
NO input (default mode is Cool)
Hotel card NO, with 1 second software delay going
from UnOcc to Occupied; 2 minute delay going from
Occupied to UnOcc.
Hotel Card NC, with 1 second software delay going
from UnOcc to Occupied; 2 minute delay going from
Occupied to UnOcc.
0342 Override Option
(only available in
non-programmable
mode)
0 0—No Override
1—Override
This option is only available for non-programmable
mode (ISU #160)
0343 Unoccupied
Heating Setpoint
(only when remote
setback enabled)
60°F 50-65°F
10-18°C
0346 Unoccupied
Cooling Setpoint
(only when remote
setback is enabled)
80°F 75-90°F
24-30°C
0347 Fan Ramping 1 0—Disabled (Lo, Med, Hi)
1—Enabled
To enable the fan ramping algorithm. Only available
for fan coil or PTAC applications (ISU #170)
0348 Fan Mode 0 0—User can choose Cycle or
Constant 3 speed: Low->Med->
High->Auto-> L o w
1—Cycle Only - Auto only
To select a particular fan mode: Auto is the fan ramp
mode. If ramping is not selected, fan mode
automatically defaults to Low Med High (Constant
only) and ISU 0348 is unavailable. Only available for
fan coil or PTAC applications (ISU #170)
Table 6. Installer Setup Menu. (Continued)
Installer
Setup
Number
Installer Setup
Name
Default
Setting All Settings Notes