LCD6000 Installation manual PAGE - 23
LCD6000_manu-inst Doc. M-184.1-LCD6000T-ENG Rev A.2 NOTIFIER ITALIA
TEC2 Programming:
First folder or Main folder (Progr. of Type ID and reading associated with the sensor)
By selecting “NO” in the function “Led Blink” the flashing
of the led on the module during the line query is disabled.
This function can be useful in such environment as
hospitals, hotels, etc.
Tracking option
Range = Configuration of highest value of the
scale (refer to Technological Range table)
A
ttention: do not change the default
datum of the relative sensitivit
y
Threshold sending = Configuration of the
operation feature
(
refer to
p
revious
p
ara
g
ra
p
h
)
.
Pre-alarm 1 threshold Programming
The default value is 10% of the selected
hi
g
hest value of the scale
The Pre-alarm 2 threshold Programming
The default value is 20% of the selected
hi
g
hest values of the scale
The alarm threshold Programming
The default value is 0% of the selected
highest value of the scale.
Sensor address
P = programmed sensor
Type ID
Press the key
F1 to program a sensor
of the previous line
Press the key
F2 to program a sensor
of the subsequent line
Press the key F3 to program
the previous sensor
Press the key F4
to program the
subsequent sensor
Programmable reading max.32 characters