3 
 
NOTE: If an EIM is mounted inside a metal cabinet, it is recommended to use 
a THM4000R1000 Wireless Adapter for extended wireless range. Mount the 
Wireless Adapter outside the metal cabinet and connect to the ABCD terminals at 
the EIM. 
NOTE: When installing multiple 
thermostats and EIMs, mount the 
EIMs at least 2 feet apart for best 
RedLINK performance.
1.1  Mount EIM. 
Mount the EIM near the HVAC 
equipment or on the equipment 
itself.
Use screws and anchors as 
appropriate for the mounting 
surface.
1.2  Wire EIM as shown. 
Refer to the table and wiring diagrams on pages 3-5.
NOTE: If you are installing discharge and return air sensors, refer to the mounting 
instructions in the Alerts and Delta T Diagnostics Installation Instructions packed 
in the kit.
1
Installing the equipment interface module (EIM)
Terminal Designations
Conventional System Heat Pump
Terminal Description Terminal Description
C
Common wire from 24 VAC 
transformer.
C
Common wire from 24 VAC 
transformer.
R*
Power wire from 24 VAC 
transformer.
R
Power wire from 24 VAC 
transformer.
RH* Heating power.  RH Heating power. 
RC* Cooling power. RC Cooling power.
W Heat Stage 1 O/B Changeover valve for heat pumps.
W2 Heat Stage 2 AUX 1
Backup Heat Stage 1/Emergency 
Heat Stage 1
W3 Heat Stage 3 AUX 2
Backup Heat Stage 2/Emergency 
Heat Stage 2
Y Compressor Stage 1 Y Compressor Stage 1
Y2 Compressor Stage 2 Y2 Compressor Stage 2
G Fan Relay G Fan Relay
A
Connect to Economizer Module or 
Lighting Panel (TOD).
L/A
Connect to Compressor Monitor, 
Zone Panel, Economizer Module or 
Lighting Panel (TOD).
* Remove jumpers when separate transformers are used.
R
C
Y
Y2
G
W
O/B
W2
AUX1
W3
AUX2
A
L/A