PW-6000 Installation
Setting Up the PW-6000 Hardware
PW-6000 (PW6K1IC) Installation and Configuration Guide, Document 800-00005V3 11
3 Setting Up the PW-6000 Hardware
The PW-6000 processor is configured with 12 jumpers and a set of 4 DIP switches.
These jumpers/switches set up the port interface, end of line termination, and
operating mode configuration. Refer to the tables below to set the jumpers as required.
3.1 Setting the Jumpers
Table 1 PW-6000 Jumper Settings
Jumpers
Set At Description
J1 N/A 10Base-T/100Base-TX Ethernet Connection (Port 0)
J2 N/A Factory Use Only
J3 OFF Port 2 RS-485 EOL Terminator is OFF
ON Port 2 RS-485 EOL Terminator is ON
J4 OFF Port 3 RS-485 EOL Terminator is OFF
ON Port 3 RS-485 EOL Terminator is ON
J5 OFF Port 1 RS-485 EOL Terminator is OFF
ON Port 1 RS-485 EOL Terminator is ON
J6 N/A Factory Use Only
J7 N/A COBOX-MICRO Ethernet Module Connection (Port 1)
J8, J9, J10 232 Port 1 is RS-232
485 Port 1 is RS-485
J11 N/A Factory Use Only
J12 N/A Factory Use Only