R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED
11 69-2467EFS—09
Flame Proven
Out of
Sequence
34
The cad cell is permanently in a low resistance state. It should typically read much higher than
20,000 ohms when no flame is present.
Set the display to display cad cell resistance.
Shield the cad cell from light.
If the display shows less than 20,000 ohms, unplug the cad cell,
If display does not read 999999 ohms, replace control.
If it does read 999999 ohms, replace cad cell.
Flame Proven
During On
Delay
23
Flame was proven during the valve on delay period. Check the oil valve for proper operation.
If the system does not have an oil valve, set the valve on delay to 0.
Flame Proven
During Off
Delay
24
Flame remained lit during the burner off delay. Check the oil valve for proper operation.
If the system does not have an oil valve, set the burner off delay to 0.
Exceeded Max
Recycles
22
Flame was lost more than the allowed number of times. The burner lights, but does not remain lit.
Check that the fuel tank is not empty.
Check the fuel supply lines (and filter) for obstructions or air
Use the pump priming feature to purge the system of airCheck
Check that the burner motor is spinning and the pump is generating adequate pressure.
If present, check operation of the oil valve.
If the problem persists, proceed to the “Cad Cell, High During Run” corrective action.
EnviraCOM™
Error
91
Communications error has been detected.
Remove all devices from the EnviraCOM™ connections, 3-pin plug and screw terminals “1-2-3”.
If the error does not clear within one minute, measure the voltage on terminals “2” and “3”.
If the voltage across terminals “2” and “3” is between 20VAC and 30VAC, replace control.
If it is outside of that range, review appliance wiring. There should be approximately 24VAC
across “2” and “3”.
Cad Cell
High During
Run
4
The cad cell resistance is higher than normal while running, the system is in need of a tune up.
Check for proper alignment of the cad cell and clean the eye if necessary.
Check if the pump is generating adequate pressure.
Check burner adjustments (refer to burner manufacturers instructions).
Check for excessive soot build up in the burner and flue.
Check for flue blockage.
Flame Proven
Late in Trial
9
The burner lit very late during the trial for ignition and is susceptible to not lighting.
Check cad cell for proper alignment and clean if necessary.
Check burner adjustments (refer to burner manufacturers instructions)
Check electrodes and spring contacts (if equipped) and adjust per manufacturers recommendations.
Check if the pump is generating adequate pressure.
Check the fuel supply lines and filter for obstructions.
Table 8. LED Flash Codes.
LED
Flash
Code
EnviraCOM™
Alarm
Number Corrective Action
1 10,5,20,59,9 The burner was not lit or lit near the end of the trial time.
Check that the manual shut off valve is open.
Check that the burner motor is spinning and the pump is generating adequate pressure.
Check the condition of the nozzle and replace if necessary.
Check the fuel supply lines and filter for obstructions or air.
Check the electrodes, spring contacts (or high voltage wires), and ignition transformer for proper operation.
If a valve is present, check for proper operation.
Check burner adjustments (refer to burner manufacturers instructions) and spark was not detected.
Check the cad cell positioning and clean the eye.
Expose the cad cell to ambient light (generally enough light to read by is adequate)
If the LED does not turn on, short the cad cell terminals,
If the LED does not turn on, replace the control,
If the LED turns on, replace the cad cell.
Shield the cad cell from light.
If the LED does not turn off, unplug the cad cell,
If the LED does not turn off, replace the control,
If the LED turns off, replace the cad cell.
Table 7. Display Alarm Information. (Continued)
Display
Alarm
EnviraCOM™
Alarm
Number Corrective Action

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell R7284B and is the answer not in the manual?

Honeywell R7284B Specifications

General IconGeneral
BrandHoneywell
ModelR7284B
CategoryControl Unit
LanguageEnglish

Related product manuals