S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL
 
บริษัท เอดีดี เฟอร์เนส จํากัด 
ADD FURNACE CO.,LTD. 
44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวีวัฒนา กรุงเทพฯ 10170 
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258 
https://www.add-furnace.com E-mail: sales@add-furnace.com 
 
 
 
 
High Humidity or Dripping Water 
Dripping water can cause the control to fail. Never install an 
appliance where water can drip on the controls.
 
In addition, high ambient humidity can damage the control.
 
If the appliance is in a humid atmosphere, make sure air circulation 
around the controls is adequate to prevent condensation. Also, 
regularly check out the system. A NEMA 4 enclosure is recommended 
for the ignition module. 
 
Corrosive Chemicals 
Corrosive chemicals can attack the module and gas control, 
eventually causing a failure. If chemicals are used for routine 
cleaning, make sure they do not reach the controls. Where 
chemicals are suspended in air, as in some industrial or agricultural 
applications, use a NEMA 4 enclosure for the ignition module.
 
 
Dust or Grease Accumulation 
Heavy accumulations of dust or grease can cause controls to 
malfunction. Where dust or grease can be a problem, provide 
covers for the module and the gas control to limit contamination. A 
NEMA 4 enclosure is recommended for the ignition module.
 
 
Heat 
Excessively high temperatures can damage controls. Make sure the 
maximum ambient temperature at the control does not exceed the 
rating of the control. If the appliance operates at very high 
temperatures, use insulation, shielding, and air circulation, as 
necessary, to protect the controls. Proper insulation or shielding 
should be provided by the appliance manufacturer; verify proper air 
circulation is maintained when the appliance is installed. 
 
INSTALLATION 
When Installing This Product… 
1. 
Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazard- ous condition.
 
2. 
Check the ratings given in these instructions to make 
sure the control is suitable for your application.
 
3. 
Installer must be a trained, experienced service 
technician.
 
4. 
After installation is complete, check out operation as 
provided in these instructions.
 
 
 WARNING
 
Fire or Explosion Hazard.
 
Can cause severe injury, death or property damage.
 
1. 
The module can malfunction if it gets wet, leading 
to accumulation of explosive gas.
 
— 
Never install where water can flood, drip or 
condense on the module.
 
— 
Never try to use a module that has been wet— replace 
it.
 
2. 
Liquefied petroleum (LP) gas is heavier than air and will 
not naturally vent upward.
 
— 
Do not operate electric switches, lights, or 
appliances until you are sure the appliance area is 
free of gas.
 
 WARNING
 
Electrical Shock Hazard.
 
Can cause severe injury, death or property damage.
 
Disconnect  power  supply  before  beginning  wiring  or 
making wiring connections to prevent electrical shock or 
equipment damage.
 
 
 CAUTION 
1. 
If a new gas control is to be installed, turn off the gas 
supply before starting installation. Conduct a Gas 
Leak Test according to the gas control manufacturer 
instructions after the gas control is installed.
 
2. 
Wiring errors can cause improper appliance 
operation and dangerous conditions such as 
bypassing safety features.
 
 
 CAUTION 
Equipment Damage Hazard.
 
Water can cause equipment damage or malfunction.
 
If the module must be mounted near water or moisture, 
provide suitable waterproof enclosure.
 
 
Maintenance Requirements in Severe 
Environments 
Regular preventive maintenance is important in any application.
 
 
 WARNING
 
Fire or Explosion Hazard.
 
May cause severe injury, death or property damage.
 
Do not attempt to take the module apart or to clean it. 
Improper reassembly and cleaning may cause unreliable 
operation.
 
 
Maintenance frequency must be determined individually for each 
application. Some considerations are:
 
• 
Cycling frequency. Appliances  that  may cycle more than 20,000 
times annually should be checked  monthly. 
• 
Intermittent use. Appliances that are used seasonally should be 
checked before shutdown and again before the next use. 
• 
Consequence  of  unexpected  shutdown.  Where  the  cost  of  an 
unexpected  shutdown  would  be  high,  the  system  should  be 
checked more  often. 
• 
Dusty, wet, or corrosive environment. Since these environments 
can cause the modules to deteriorate more rapidly, the system 
should be checked more often. 
 
Any module should be replaced if it does not perform properly on 
checkout or troubleshooting. In addition, replace any module if it 
is wet or looks like it has ever been wet. Protective enclosures as 
outlined under “Planning the Installation” are recommended 
regardless of checkout frequency.
 
 
Location 
The mounting location must provide:
 
— 
Good, clear access to 
the field wiring terminals.