Troubleshooting Guide 
Refer to the following guide for troubleshooting (Fig. 14).
 
 
NOTE: “CALL FOR HEAT” 24 VAC SUPPLY IS CONNECTED TO THE 24 V TERMINAL ON THE CONTROL.
 
 
 
NO
 
 
YES
 
 
30 SECOND 
PREPURGE 
NO
 
DELAY?(S8670
 
ONLY)
 
 
YES
 
NO
 
 
 
 
YES
 
YES
 
 
 
SPARK
 
STOPS WHEN
 
 
 
 
  
PILOT IS 
NO 
LIT?
 
 
YES
 
 
 
 
  
NO
 
 
YES
 
 
 
SYSTEM
 
RUNS UNTIL “CALL 
NO 
FOR HEAT”
 
ENDS? 
YES
 
 
 
 
YES
 
Fig. 14. Troubleshooting Guide.
 
 
M29921
 
TURN GAS SUPPLY OFF. 
TURN THERMOSTAT 
(CONTROLLER)TO “CALL 
FOR HEAT.”
 
 
TURN GAS SUPPLY ON AND 
RECYCLE “CALL FOR HEAT.”
 
CHECK  FOR PROPER THERMOSTAT  (CONTROLLER) OPERATION.
 
REMOVE MV LEAD AT MODULE. IF VALVE CLOSES, RECHECK TEMPERATURE CONTROLLER AND WIRING. IF NOT, REPLACE 
GAS  CONTROL.
 
START
 
BEFORE TROUBLESHOOTING, 
FAMILIARIZE YOURSELF WITH THE 
STARTUP AND CHECKOUT 
PROCEDURES.
 
CHECK LINE VOLTAGE POWER, LOW VOLTAGE TRANSFORMER, LIMIT CONTROLLER, THERMOSTAT (CONTROLLER), AND WIRING. ALSO, 
CHECK AIR PROVING SWITCH ON COMBUSTION AIR BLOWER SYSTEM (IF USED) AND THAT THE VENT DAMPER END SWITCH (IF USED) IS 
MADE.
 
CHECK  IGNITION CABLE, GROUND WIRING, CERAMIC  INSULATOR, AND SPARK GAP AND CORRECT.
 
CHECK BOOT OF THE IGNITION CABLE FOR SIGNS OF MELTING OR BUCKLING. TAKE PROTECTIVE ACTION TO SHIELD CABLE 
AND BOOT  FROM EXCESSIVE TEMPERATURES.
 
CHECK THAT ALL MANUAL GAS VALVES ARE OPEN, SUPPLY TUBING AND PRESSURES ARE GOOD, AND PILOT BURNER 
ORIFICE IS NOT BLOCKED (PILOT GAS FLOWING).
 
CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND PILOT OPERATOR ON GAS CONTROL.
 
CHECK FOR 24 VAC ACROSS PV-MV/PV TERMINALS ON MODULE. IF VOLTAGE IS OKAY, REPLACE GAS CONTROL. IF NOT, 
REPLACE  MODULE.
 
NOTE: IT MAY BE NECESSARY TO RECYCLE THE “CALL FOR HEAT” MORE THAN ONCE TO CLEAR THE PILOT SUPPLY TUBES OF AIR.
 
NOTE: IF CONTROL GOES INTO LOCKOUT OR RETRY DELAY, RESET THE “CALL FOR HEAT.” 
CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE.
 
CLEAN FLAME ROD.
 
CHECK ELECTRICAL CONNECTIONS BETWEEN FLAME ROD AND MODULE. 
CHECK FOR CRACKED CERAMIC FLAME ROD INSULATOR.
 
CHECK THAT PILOT FLAME COVERS FLAME ROD AND IS STEADY AND BLUE. 
ADJUST PILOT FLAME.
 
IF PROBLEM PERSISTS, REPLACE MODULE.
 
CHECK FOR 24 VAC ACROSS PV-MV/PV TERMINALS ON MODULE. IF NO VOLTAGE, REPLACE MODULE.
 
CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND GAS CONTROL INCLUDING SAFETY CONTROLS WIRED IN THE CIRCUIT. IF 
OKAY, REPLACE GAS CONTROL.
 
NOTE: IF CONTROL GOES INTO LOCKOUT OR RETRY DELAY, RESET THE “CALL FOR HEAT.” 
CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE.
 
NOTE: IF GROUND IS POOR OR ERRATIC, SHUTDOWNS MAY OCCUR OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL 
AT THE TIME OF CHECKOUT.
 
CHECK THAT PILOT FLAME COVERS FLAME ROD AND IS STEADY AND BLUE. PILOT FLAME MUST NOT BE MOVING AROUND DUE TO 
OUTSIDE AIR FLOWS, ETC.
 
ADJUST PILOT FLAME. CHECK GAS PRESSURE MEETS APPLIANCE SPECIFICATIONS WHILE APPLIANCE MAIN BURNER ON AND ALL 
OTHER GAS APPLIANCES ON THE SUPPLY ARE OPERATING AT FULL RATE.
 
IF CHECKS ARE OKAY, REPLACE MODULE.