SiXCOMBO  Combination Smoke/Carbon Monoxide (CO) Detector / Combinación de detector de Humo/Monóxido de carbono (CO) 
Quick Installation Guide  Guía Rápida de Instalación 
 
This device is intended for use with Honeywell controls that support SiX series 
devices including the SiXCOMBO. Check the control for compatibility with this 
device. This device occupies 3 control panel zones, one zone for each service 
(smoke detection, heat detection, carbon monoxide detection). 
NOTE: This device must be installed by a qualified technician. 
 
FEATURES 
•  Multi-Criteria Sensing: uses four sensing elements to react faster while 
minimizing false alarms: 
  - Photoelectric smoke sensor detects airborne smoke particles 
  - Carbon Monoxide (CO) sensor detects smoldering fires 
  - Infrared (IR) sensor measures ambient light and flame signatures, such as 
flame flicker 
  - Thermal detection monitors for dangerous rise in temperature 
•  CO Detector End-of-Life reporting (detector needs replacing) 
•  Smoke detector maintenance reporting (detector needs cleaning or replacing) 
•  Low Battery Detection 
•  One Go / All Go: all smoke/CO detectors in the system programmed as one-go-
all-go will sound on alarm. 
•  Voice announcements (English only) 
 
Installation Instructions (800-22142 – https://mywebtech.honeywell.com/) and 
Limitations of Fire Alarm Systems Insert (800-15144 12/15) and System Smoke 
Detectors Application Guide
 (SPAG9101 7/12). 
LED INDICATORS 
The SiXCOMBO Smoke/CO detector has a multi-color top LED:   
Green =  Supervisory indication; blinks during power on, reset, and during normal 
operation 
Amber =  Signal maintenance and trouble events 
Red =   Alarm condition (either Smoke or CO) 
Side LED windows indicate alarms:  
Red = smoke alarm 
Blue = CO alarm
 
 
 
 
 
 
 
 
 
 
 
Este producto está diseñado para ser usado en controladores Honeywell que 
soportan dispositivos de la serie SiX incluido el SiXCOMBO. Compruebe la 
compatibilidad del control con este dispositivo. Este dispositivo ocupa 3 zonas del 
panel de control, una para cada servicio (detección de humo, detección de calor, 
detección de monóxido de carbono). 
NOTA: Un técnico cualificado debe instalar este dispositivo. 
 
CARACTERISTICAS  
•  Detección multi-criterio: Utiliza cuatro elementos de detección para una más 
rápida reacción mientras se minimizan falsas alarmas: 
  - Sensores fotoeléctricos de humo que detectan partículas de humo en el aire 
  - Sensores de detección de Monóxido de Carbono (CO) para detección de 
incendios sin llama 
  - Sensores infrarrojos (IR) que detectan luces de ambiente y señales de flamas 
tales como movimiento de las llamas 
  - Detección termal que monitorea aumento peligroso de temperaturas 
•  Fin de vida útil del detector de CO (el detector necesita ser remplazado) 
•  Reporte d
e mantenimiento del sensor de humo (Cuando el sensor requiere limpieza 
or replacing) 
•  Detección de batería baja. 
•  Uno se activa / Todos se activan: todos los detectores de humo/CO en el sistema 
programados como “uno se activa/todos se activan”, sonarán su propia alarma 
•  Avisos de voz (únicamente en inglés) 
 
Vea la guía de instalación de Honeywell (800-22142- 
https://mywebtech.honeywell.com/) y el inserto de las limitaciones de sistemas de 
alarma de fuego. (800-15144SP 12/15). Consulte la Guía de aplicación de detectores 
de humo del sistema (SPAG9101 7/12).
 
 
INDICADORES DE LED 
El detector de humo/Monóxido de carbono SiXCOMBO contiene un LED multicolor:  
Verde = Indicador de supervisión; parpadea durante iniciación, reinicio y durante 
operación normal. 
Ámbar = Señal de eventos de mantenimiento o problemas 
Rojo = Condición de alarma (de humo o monóxido de carbono) 
Ventanas de LED laterales: Rojo = Humo, Azul = Monóxido de carbon 
 
ENROLLMENT  REGISTRO 
• Once enrolled, the device cannot be us
until it is removed from the current controller. See the 24-hour 
Enrollment Deletion section below or the controller’s 
instructions. 
 
Enroll the Device Services (Smoke, Heat, CO) 
1. Remove the detector from the base plate. 
2. Put the control panel in Programming mode. 
  For Lyric Controller: Security > Tools [installer code] > 
Program > (scroll down) > SiX Programming 
3. Pull the battery tab to activate enrollment process (be sure 
batteries are seated properly to avoid a false low battery 
condition). If the battery tab has already been removed and 
the unit is powered up, press either Test switch for less 
than 3 seconds to activate the enrollment process. 
4. The device attempts enrollment (green LED flashes about 8 
seconds). If successful, the green LED lights steady for 3 
seconds and the device announces successful enrollment. 
  If the LED does not light steady, enrollment failed. Retry by 
pressing either Test switch for less than 3 seconds. 
  All services (Smoke, Heat, and CO) are enrolled in 
sequential (or next available) zone numbers with the 
following default attributes: 
 
  NOTE: Maintenance and CO End-of-Life are automatically 
enrolled for the respective smoke and CO zones. Upon 
either of these conditions, Contact ID code E386 “Low 
Maintenance Smoke” is sent for the respective zone. 
  Supervision: Detector supervision is factory set for 1 
minute and is not programmable. 
 
5. To assign zone descriptors for each of the zones and/or 
change device type or zone response type, select the zone 
then select Edit and make the desired changes. Press 
Save when done. 
 
24-Hour Enrollment Deletion 
Use this procedure within 24 hours of initial enrollment to delete 
this device from the controller. This allows reenrollment in a 
specific controller in case enrollment in that controller failed 
(i.e., the device inadvertently enrolled in a different controller). 
This resets the device to factory default settings and removes 
the communication link data in the controller in which it is 
enrolled, allowing the device to be reenrolled in the desired 
controller. 
1.  Press and hold both the Smoke and CO test switches 
simultaneously for 5 seconds, then release. The green light 
flashes rapidly.  
2. Press and hold both buttons again for one second and 
release.
 
 
 
OPEN / ABIERTO 
 
Operation Modes / Modos de operación 
MODE /  MODO 
Status LED (Top) /
Estado del LED 
(Side) / Ventana 
Sounder / 
Sonador 
Speaker / Bocina 
First Time 
 Power Up / 
Encendido 
Blink Green, every 
2 secs/ Parpadea 
verde cada  
2 segundos 
Dark / 
Apagado 
Silent / 
Silencio 
instructions after 
first time power-up 
or after default 
/ Bienvenida de 
voz, seguido por 
las instrucciones 
POR para la 
selección de 
lenguaje, 
enrolamiento, 
Normal (Standby) 
/ 
Estado normal 
every 10 sec / 
parpadeo verde 
Dark / 
Apagado 
Silent / 
Silencio 
Silent / 
Silencio 
Smoke Alarm / 
Alarma de humo 
Blink Red every 10 
secs / parpadeo rojo 
cada 10 segundos
Blink Red / 
Parpadeo rojo 
Temp-3 
evacuate”/ 
“Advertencia, 
Thermal Alarm / 
Alarma termal 
Blink Red e
very 10    
secs / parpadeo rojo 
cada 10 segundos
Blink Red / 
Parpadeo rojo 
Temp-3 
evacuate”/ 
“Advertencia, 
CO Alarm / Alarma 
de monóxido de 
carbono 
Blink Red every 10    
secs / parpadeo rojo 
cada 10 segundos
 
Blink Blue / 
Parpadeo azul 
Temp-4 
monoxide, move 
to fresh air” / 
Advertencia, 
monóxido de 
carbón, pasar al 
 
TO SILENCE THE DETECTOR 
Press the test switch. The detector sounds again after 5 minutes if the 
alarm condition continues. 
 
PARA SILENCIAR EL DETECTOR 
Presione el interruptor de prueba. El detector volverá a sonar después 
de 5 minutos si continúa la condición que originó la alarma. 
• Una vez registrado, el dispositivo no se puede usar con otro 
sistema hasta que sea removido del controlador actual. 
Consulte la sección «Eliminación del registro dentro de las 24 
horas» a continuación o las instrucciones del controlador. 
 
Registre los Servicios de los Dispositivos (Humo, 
Calor, CO) 
1. Desmonte el detector de la placa de la base (debe haber una 
falla en el interruptor de seguridad al momento de registrarlo). 
2. Coloque el panel de control en el modo Programación de 
Zona. 
  Para el Controlador Lyric: Seguridad > código de 
instalador > Programa > (desplazarse hacia abajo) > 
Programación SiX 
3. Tire de la lengüeta de la batería para activar el proceso de 
registro (asegúrese de que las baterías estén bien colocadas 
para evitar una falsa condición de batería baja). Si ya retiró 
la lengüeta de la batería y la unidad está encendida, pulse el 
interruptor de Prueba durante menos de 3 segundos para 
activar el proceso de registro. 
4. El dispositivo intenta hacer el registro (el LED verde 
parpadea aproximadamente por 8 segundos). Si el proceso 
se realiza exitosamente, el LED verde se ilumina de forma 
continua durante 3 segundos y el dispositivo anuncia que el 
registro se ha realizado correctamente. 
  Si el LED no se ilumina de forma continua, el registro ha 
fallado. Vuelva a intentarlo oprimiendo cualquiera de los dos 
interruptores de Prueba durante menos de 3 segundos. 
  Todos los servicios (Humo, Calor y CO) se registran 
automáticamente en números de zona secuenciales (o los 
siguientes disponibles) con los siguientes valores 
predeterminados: 
Tipo de respuesta por 
zona 
Incendio sin verificación 
Incendio sin verificación 
Detector de monóxido 
de carbono 
 
  NOTA: El mantenimiento y el CO de Fin de Vida se registran 
de forma automática en las respectivas zonas de humo y 
CO. Bajo cualquiera de las dos condiciones, se envía el 
código de identificación de contacto E386 «Humo bajo para 
mantenimiento» a la zona respectiva. 
  Supervisión: La supervisión del detector viene configurada 
de fábrica por 1 minuto y no es programable. 
 
5. Para asignar descriptores de zona para cada una de las 
zonas y/o cambiar el tipo de dispositivo o la respuesta por 
zona, seleccione la zona y luego seleccione Editar y realice 
los cambios deseados. Oprima Guardar al terminar. 
 
Eliminación del registro dentro de las 24 horas 
Para eliminar este dispositivo del controlador, siga este 
procedimiento dentro de las 24 horas posteriores al registro 
inicial. Esto permite el registro en un controlador específico en 
caso de que el registro falle en dicho controlador (es decir, 
registrar el controlador de forma inadvertida en otro controlador). 
Esto reinicia el dispositivo a su configuración predeterminada de 
fábrica y elimina los datos del enlace de comunicación en el 
controlador en el que está registrado, lo que permite registrar el 
dispositivo nuevamente en el controlador deseado. 
1.  Presione simultáneamente los botones de prueba de humo y 
de CO durante 5 segundos y libérelos. La luz verde 
parpadeará rápidamente.  
2. Vuelva a presionar ambos botones simultáneamente y 
MOUNTING 
After enrolling, verify adequate signal strength 
by conducting Go/No Go tests (see the 
controller’s instructions) with the device in its 
intended mounting location. Adjust the device 
location and orientation as necessary.
 
 
 
 
Si el dispositivo no está en su ubicación final 
de montaje cuando se registre, realice 
pruebas de Va/No Va (vea las instrucciones 
del controlador) para verificar que la 
intensidad de la señal sea adecuada. Ajuste 
la ubicación y orientación del dispositivo 
según ea necesario.