T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
63-7147—05 6
T775 OPERATIONS
Integral Action
“Droop” and equipment hunting can be minimized by 
summing (integrating) the offset errors over time and adding 
this correction to the output voltage.
A non-zero value for the integral time will allow the controlled 
temperature to try and reach the setpoint value.
The integral time is factory set for 400 seconds and is similar 
to the response time of the T775 Series 1000 models. This is 
a good middle range and should satisfy many applications. 
The integral time can be increased for applications where 
sensed response is slow, and can be decreased for 
applications where sensed response is fast (e.g. discharge air 
control).
As a starting point, an optimal integral time for discharge air 
typically ranges from 12 to 200 seconds. An optimal integral 
time for room control typically ranges from 60 to 2,500 
seconds. The purpose of integral action is to reduce or 
eliminate the offset from setpoint during steady state control 
that is often seen in proportional-only control.
Keep in mind that the controller is most sensitive to throttling 
range. Adjust the throttling range first before making any 
adjustment to integral time. Adjust throttling range to be as 
wide as possible to start, because this will provide the most 
stable control. Remember that the integral will eliminate the 
steady state error so you do not need to have a small throttling 
range to have accurate control. (Integral action allows for 
controlling to setpoint even with a wide throttling range.)
Derivative Action
Proportional-integral-derivative (PID) control adds the 
derivative function to PI control. The derivative function 
opposes any change and is proportional to the rate of change. 
The more quickly the control point (actual sensed 
temperature) changes, the more corrective action the PID 
system provides.
If the control point moves away from the setpoint, the 
derivative function outputs a corrective action to bring the 
control point back more quickly than through integral action 
alone. If the control point moves toward the setpoint, the 
derivative function reduces the corrective action to slow down 
the approach to the setpoint, which reduces the possibility of 
overshoot. The rate time setting determines the effect of the 
derivative action. The rate time is the time interval by which 
the derivative function advances the effect of the proportional 
action. In T775 controllers, the derivative rate time can range 
from 0 to 3,600 seconds. The higher the derivative setting, the 
greater the effect.
For all T775 Series 2000 controllers, the derivative default 
value is factory set to zero (no derivative control). It is strongly 
recommended that the derivative remain at zero (0) unless 
you have a very good reason to adjust it. Derivative control is 
not needed in the vast majority of HVAC applications.
Differential vs. Throttling Range
Differential is used for relay outputs, and throttling range is 
used for modulating outputs.
Setpoint and Differential
The following describes the relationship between setpoint and 
differential for heating and cooling. These settings are 
programmed for each output relay.
HEATING MODE SETPOINT AND DIFFERENTIAL
In heating mode, the differential is below the setpoint. The 
relay de-energizes when the temperature rises to the setpoint. 
As the temperature drops to the setpoint minus the 
differential, the relay energizes.
COOLING MODE SETPOINT AND DIFFERENTIAL
In cooling mode, the differential is above the setpoint. The 
relay de-energizes when the temperature falls to the setpoint. 
As the temperature rises to the setpoint plus the differential, 
the relay energizes.
Throttling Range
The throttling range brackets the setpoint setting, e.g., if the 
setpoint is 72° F (22° C) and the throttling range is 10° F 
(-12° C), then the effective throttling temperature range is 
67° to 77° F (19° to 25° C) . This applies to both modulating 
outputs and floating outputs.
Throttling Range for Modulating High or 
Low Limit 
On models that support this feature, the throttling range for 
the modulating high or low limit positions the setpoint at the 
end of the throttling range. For example, with a high (Heat) 
limit at Sensor B of 200° F (93° C) and a throttling range of 
10° F (-12° C), the modulating output controlling Sensor A 
begins to throttle back at 190° F (88° C), and fully closes at 
200° F (93° C). Conversely, the throttling range for the low 
limit begins above the Cooling setpoint in the same manner.
Setpoint High Limit
You can set an irreversible setpoint high limit maximum value 
for any single setpoint temperature value. This prevents the 
user from setting any setpoint above the chosen high setpoint 
limit, which is useful for meeting some local codes.
Adjust the setpoint (at any output) to the desired maximum 
setpoint. Then, simultaneously press the HOME, , and  
buttons, and continue to press all three buttons for five 
seconds to set the setpoint high limit maximum to this value.
NOTE: You must press all three buttons at exactly the same 
time for this action to occur.
IMPORTANT
1. This action sets the maximum setpoint value of all 
outputs to the setpoint high limit maximum.
2. Setting the high limit setpoint maximum is 
irreversible. If you perform the action inadvertently 
and this setpoint adversely affects the control of your 
system, you must replace the controller.