T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
62-0257—11 18
Fig. 38. Setup - Outputs - Loop 1 - Number of Relays.
1.3.4.1. Number of RELAYS
1. From the Loop 1 menu, use the and  buttons to 
highlight # RELAYS.
2. Press the  button to display the number of relays.
3. Use the  and  buttons to select the number of 
relays depending on setup. (SeeSee “1.3.1. Num-
ber of RELAYS” on page 14.)
4. Press the  button to accept the value and display 
the Loop 1 menu.
Fig. 39. Setup - Outputs - Loop 1 - Integral.
1.3.4.2. INTEGRAL
1. From the Loop 1 menu, use the and  buttons to 
highlight INTEGRAL.
2. Press the  button to display the integral value.
3. Use the  and  buttons to change the integral 
time from 0 to 3,600 seconds in increments of 10 
seconds.
Default: 400 seconds
Range: 0 to 3,600 seconds
4. Press the  button to accept the value and display 
the Loop 1 menu.
NOTES:
1. The Integral time is factory set for 400 seconds. This 
is a good middle range and should satisfy many 
applications. The integral time can be increased for 
applications where sensed response is slow, and can 
be decreased for applications where sensed 
response is fast (e.g. discharge air control).
2. As a starting point, an optimal integral time for 
discharge air typically ranges from 12 to 200 
seconds. An optimal integral time for room control 
typically ranges from 60 to 2,500 seconds. The 
purpose of integral action is to reduce or eliminate 
the offset from setpoint during steady state control 
that is often seen in proportional only control.
3. Keep in mind that control is most sensitive to 
throttling range. Adjust the throttling range first 
before any adjustment to integral time. Adjust 
throttling range to be as wide as possible to start 
since this will provide the most stable control. 
Remember that the integral will eliminate the steady 
state error so you do not need to have a small 
throttling range to have accurate control. (Integral 
action allows for controlling to a setpoint even with a 
wide throttling range).
Fig. 40. Setup - Outputs - Loop 1 - Derivative.
1.3.4.3. DERIVATIVE
The Derivative default value is factory set to zero (no 
derivative control). It is strongly recommended that the 
derivative remain at zero (0) unless you have a very good 
reason to adjust it. Derivative control is not needed in the 
vast majority of HVAC applications.
1. From the Loop 1 menu, use the and  buttons to 
highlight DERIVATIVE, then press the  button to 
display the derivative seconds.
2. Use the  and  buttons to increase/decrease the 
value.
Default: 0 (zero)
Range: 0 to 3,600 seconds
3. Press the  button to accept the value and display 
the Loop 1 menu.
ENTER
NUMBER OF
RELAYS FOR
LOOP 1
SETUP
OUTPUTS
LOOP 1
# RELAYS
3
SETUP
 OUTPUTS
 LOOP 1
 # RELAYS
M24446
SETUP
  OUTPUTS
 LOOP 1
   INTEGRAL
SETUP
OUTPUTS
LOOP 1
INTEGRAL
400
SEC
ENTER
INTEGRAL
TIME
FOR
LOOP 1
M24447
SETUP
  OUTPUTS
 LOOP 1
   DERIVATIV
SETUP
OUTPUTS
LOOP 1
DERIVATIV
0
SEC
ENTER
DERIVATIVE
TIME
FOR
LOOP 1
M24448