T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
17 62-0257—11
Fig. 34. Setup - Outputs - Options - Show Runtime.
1.3.3.4. SHOW RT (show run time hours)
1. Press the  button to display the Show RT values.
2. Use the  and  buttons to select YES or NO.
Default: YES
3. Press the  button to accept the value and return to 
the Options menu.
A limited feature in the T775L, selecting YES shows the 
run time hours only of independent relays if they are 
among the first four relays. Runtime of relays in a loop 
cannot be shown. 
NOTE: Run times can be reset to zero for each of the 
first four independent relays. You must do this for 
each relay that you want to reset to zero. See 
“1.3.5.3. RESET RT (Run Time)” on page 21.
Fig. 35. Setup - Outputs - Sync.
1.3.3.5. SYNC (synchronize setpoint changes)
1. Press the  button to display the Sync values.
2. Use the  and  buttons to select YES or NO.
Default: NO
3. Press the  button to accept the value and return to 
the Options menu.
Selecting YES causes all setpoints for all loops and 
relays to sync to any change to loop
For example, assume the LOOP1 setpoint is 110°F, 
LOOP2 is 115°F, and RELAY9 is 120°F. With SYNC=YES, 
when the LOOP1 setpoint is adjusted to 112°F (increase 
2°F), then LOOP2 and all other relay setpoints increase 
by 2°F. Thus the LOOP2 setpoint is now 117°F and the 
RELAY9 setpoint is 122°F. 
Fig. 36. Setup - Outputs - Options - Exit.
1.3.3.6. Exit Options Setup
Press the  button (or highlight EXIT and press the  
button) to exit and return to the Outputs menu.
Continue with “1.3.4. Setting up the Loops”
Fig. 37. Setup - Outputs - Loop 1 Menu.
1.3.4. Setting up the Loops
1. From the Outputs menu, use the  and  buttons 
to highlight the desired loop (1 or 2 depending on 
configuration).
2. Press the  button to display the selected loop 
menu.
Continue with the remainder of this section to
setup the loops.
SETUP
 OUTPUTS
 OPTIONS
 SHOW RT
SETUP
OUTPUTS
OPTIONS
SHOW RT
SHOW
RUN TIME
FOR
RELAYS
YES
NO
M24443
SETUP
 OUTPUTS
 OPTIONS
 SYNC
SETUP
OUTPUTS
OPTIONS
SYNC
ALL
SETPTS
CHANGE
NO
YES
M28657
SETUP
 
OUTPUTS
  OPTIONS
SETUP
OUTPUTS
OPTIONS
USE SCHED
MIN OFF
MIN ON
DI OPTS
SHOW RT
SYNC
EXIT
M24520A
SETUP
 
OUTPUTS
  LOOP 1
SETUP
OUTPUTS
LOOP 1
# RELAYS
INTEGRAL
DERIVATIV
ON DELAY
OFF DELAY
SCHEDULE
RESET
EXIT
M24445