T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
62-0257—11 16
Fig. 32. Setup - Outputs - Min On/Off Options.
1.3.3.2. MIN OFF or MIN ON
This is the minimum number of seconds of “off time” or 
“on time” for all relays that are not configured in a loop.
1. Press the  button to display the Min Off /On value.
2. Use the  and  buttons to increase/decrease the 
desired number of seconds from 0 to 990 seconds 
in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3. Press the  button to accept the seconds and 
display the DI OPTS menu.
NOTES:
1. The minimum OFF or ON time applies to all 
relays that are not configured in a loop.
2. When minimum OFF or ON time is active, relays 
waiting to be energized display a flashing 
square underneath the relay number on the 
home screen.
3. If the minimum off time is not equal to zero (0), 
the minimum off time activates at power-up. 
4. To manually override, press the  button.
Fig. 33. Setup - Outputs - Options - DI Options.
1.3.3.3. DI OPTIONS (digital input options)
The DI Option that you select applies to all outputs. This 
option overrides any Setpoint/Setback values entered in 
the Schedule.
1. Press the  button to display the DI Option
selections.
2. Use the  and  buttons to highlight DISABLE, 
SETBACK, or IGNORE.
Default: DISABLE
3. Press the  button to accept the value and display 
the SHOW RT menu.
When the digital input (DI) closes, all outputs follow the DI 
option value (Disable, Setpoint, Setback, Enable, DHW, 
or Ignore):
• DISABLE disables the outputs; relays return to de-
energized state.
• SETPOINT forces the control to the setpoint 
temperature.
• SETBACK enables a setback temperature value to be 
programmed for each output and forces the control to 
the setback temperature.
— To program the Setback temperature without 
Reset, see Fig. 58 on page 24.
— To program the Setback temperature with Reset, 
see Fig. 69 on page 28.
• ENABLE energizes all relays to 100%. Use this option 
carefully.
• DHW: if a reset curve is being used, then the controlled 
setpoint becomes the maximum setpoint (either SP 
MAX A1 or BOILR MAX). If a reset curve is not being 
used, then DI closure for DHW has no effect.
• IGNORE causes the digital input to have no effect on 
the Relay outputs.
      SETUP
      OUTPUTS
 OPTIONS
 
ENTER
MINIMUM
OFF TIME
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
MIN OFF
0
SEC
M24522A
OR
MIN ON
ENTER
MINIMUM
ON TIME
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
MIN ON
0
SEC
MIN OFF
SETUP
 OUTPUTS
 OPTIONS
 DI OPTS
SETUP
OUTPUTS
OPTIONS
DI OPTS
SELECT DI
OPTION
FOR
RELAYS
DISABLE
SETPOINT
SETBACK
ENABLE
DHW
IGNORE
M24442A