T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
62-0257—11 20
Fig. 44. Setup - Outputs - Loop 1 - Reset.
1.3.4.7. RESET (Loop Reset)
This selection enables the controller’s Reset function, and 
allows each output to be individually programmed for 
Reset or No Reset.
IMPORTANT
To use the Reset function of the controller, the 
first loop must be set for Reset.
The RESET choice is offered for all outputs in setup 
mode, and you can set any or all of them for Reset=YES 
or Reset=NO. The default is Reset=NO.
For the remaining outputs, if Reset=YES, then these 
outputs use the reset curve programmed for the first 
output.
1. From the Loop 1 menu, use the and  buttons to 
highlight RESET.
2. Press the  button to display the value.
Default: NO
3. Use the  and  buttons to select the value.
4. Press the  button to accept the value and display 
the Loop 1 menu.
• If you select YES, then the second loop (and any 
additional relays) display this Setup option.
• If you select NO, then No Reset is configured.
Fig. 45. Setup - Outputs - Loop 1 - Exit.
1.3.4.8. Exit Loop Setup
Use the  and  buttons to highlight EXIT and press the 
 button.
If you have additional relay outputs, continue with “1.3.5. 
Setting up the Relays”. Otherwise, go to “1.4. Exiting 
Setup” on page 22
Fig. 46. Setup - Outputs - Relay Menu.
1.3.5. Setting up the Relays
1. From the Outputs menu, use the  and  buttons 
to highlight the desired relay.
2. Press the  button to display the selected relay 
menu.
NOTE: There can be up to two additional relays. 
For example: If there are 12 total relays, and 
Loop 1 uses relays 1–4, and Loop 2 uses relays 
5–8, the two available additional relays will be 9 
and 10. (In this example, relays 11 and 12 are 
not usable since there can be only two additional 
relays.)
Continue with the remainder of this section to setup the 
relay outputs.
SETUP
 OUTPUTS
 LOOP 1
 RESET
SETUP
OUTPUTS
LOOP 1
RESET
USE
RESET
FOR
LOOP 1
YES-BOILER
YES-OTHER
NO
M24452
SETUP
 
OUTPUTS
  LOOP 1
SETUP
OUTPUTS
LOOP 1
# RELAYS
INTEGRAL
DERIVATIVE
ON DELAY
OFF DELAY
SCHEDULE
RESET
EXIT
M24453
SETUP
 
OUTPUTS
  RELAY 9
SETUP
OUTPUTS
RELAY 9
SCHEDULE
RESET
RESET RT
EXIT
M24454