T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
21 62-0257—11
Fig. 47. Setup - Outputs - Relay - Schedule.
1.3.5.1. SCHEDULE
This selection displays only if “Use Sched = YES” is 
selected during the Output Options setup (see page 15). 
When selected, individual outputs default to follow the 
schedule.
1. Press the  button to display the Schedule values.
2. Use the  and  buttons to select YES or NO.
Default: YES
3. Press the  button to accept the value and return to 
the Relay menu.
NOTE: If USE SCHED = YES, then the default is YES. 
See “1.3.3.1. USE SCHED” on page 15.
An individual output can be selected to be controlled or 
not controlled by the schedule.
If NO is selected, the Setback selection does not appear 
in the Program menu for this output.
Fig. 48. Setup - Outputs - Relay - Reset.
1.3.5.2. RESET (Relay Reset)
This selection enables or disables reset for the selected 
relay.
IMPORTANT
To use the Reset function of the controller, the 
first Loop must be set for Reset.
1. Press the  button to display the Reset values.
2. Use the  and  buttons to select YES or NO.
Default: NO
3. Press the  button to accept the value and return to 
the Relay menu.
• If you select YES, then the second relay (if available) 
displays this Setup option and uses the reset curve 
programmed for the first output Loop.
• If you select NO, then No Reset is configured for the 
remaining relay output. 
Fig. 49. Setup - Outputs - Relay - Reset Runtime.
1.3.5.3. RESET RT (Run Time)
This selection displays only if “Show RT = YES” is 
selected during Output Options setup (see page 17).
1. Press the  button to display the Reset RT values.
2. Use the  and  buttons to select YES or NO.
Default: NO
3. Press the  button to accept the value and return to 
the Relay menu.
Selecting YES immediately resets the output run time 
hours to zero for this output. When you subsequently 
return to this screen, the RESET RT defaults to NO.
NOTE: Run times can be reset to zero for each of the 
first four independent relays. You must do this for 
each relay that you want to reset to zero.
SETUP
 OUTPUTS
 RELAY 9
 SCHEDULE
SETUP
OUTPUTS
RELAY 9
SCHEDULE
USE
SCHEDULE
FOR
OUTPUTS
YES
NO
M24455
SETUP
OUTPUTS
RELAY 9
RESET
USE
RESET
FOR
RELAY 9
YES
NO
SETUP
 OUTPUTS
 RELAY 9
 RESET
M24456
SETUP
 OUTPUTS
 RELAY 9
 RESET RT
SETUP
OUTPUTS
RELAY 9
RESET RT
RESET
RUN TIME
FOR
RELAY 9
YES
NO
M24457