INSTALLATION INSTRUCTIONS
TR21-WS, TR23-WS, TR21-WK,
TR23-WK, WRECVR
APPLICATION
The WRECVR receiver and TR21-WS, TR23-WS, TR21-WK,
and TR23-WK are a family of wireless wall modules and
receiver for use with:
Spyder Unitary Controllers: PUL, PVL, etc.
Excel 10 W7750, W7751, W7752, and W7753
controllers
T7350, T7351, and TB8575 low-voltage SuitePRO™
thermostats
Will not work with TB7220, TB8220 or TB line voltage
thermostats, XL15s, W7762, W7763 or certain other
XL controllers,
Will work with WEBs-AX™ I/O Module products if
using a separate transformer
Compatibility with various other non-Honeywell con-
trollers that accept 10K type2 NTC temperature inputs
NOTE: Refer to the TR21 and TR23 Wall Modules –
Specification Data, form 63-1332, for specific model
features and additional information.
FEATURES
Wall module to Receiver (point to point) wireless kits
can replace any standard wired sensor
Wireless Kits (wall module and receiver) are pre-bound
at the factory for quick installation
Signal Strength LED built into the wall module
Low battery indication
Optional dip switches available to bind any wall
module to any receiver
Approximate 5 year battery life with AA Alkaline
(included), 7.5 year with Lithium
Locking screw discourages tampering and battery
theft.
SPECIFICATIONS
Models: For specific model information, see Specification
Data, form 63-1332.
Environmental Ratings:
Wall Module Operating Temperature: 45° to 99°F
(7° to 37°C).
Receiver Operating Temperature: -40° to 150°F
(-40° to 65.5°C).
Storage Temperature: -40° to 150°F (-40° to 65.5°C).
Operating Humidity: 5% to 95% RH (non-condensing)
Accuracy: +/- 1ºF (+/- 0.5ºC) across 12ºC to 30ºC
Setpoint Range for TR23: 56° to 84°F (13° to 29°C)
Accessories: 50007298-001 (pack of 12) medium, cover
plate; 6-7/8 x 5 in. (175 x 127 mm).
Power:
Receiver Voltage: 20 – 30VAC/DC, 50/60Hz; 24VAC typical
Housing:
Wall Module: UL94-HB
Receiver: UL94-5VA
Radio Frequency 2.4 GHz (IEEE Std 802.15.4-2003
compliant)
Open Range: 3000 feet
Typical Range: 100 feet
Output power: 16dBm
Receiver power consumption: <1.5 VA@24VAC
Model No. FCC/IC ID’s
TR21-WS
FCC ID: HS9WLKFWM
IC: 573R-WLKF
TR21-WK
TR23-WS
TR23-WK
TR21-WSU
TR23-WSU
WRECVR
FCC ID: HS9WLKFRV
IC: 573R-WLKF
WRECVRU
“Este equipamento opera em caráter
secundário, isto é, não tem direito à proteção
contra interferência prejudicial, mesmo de
estações do mesmo tipo, e não pode causar
interferência a sistemas operando em caráter
primário.
62-0291-09
(01) 07898911288524
2969-10-6617
Agência Nacional de Telecomunicações
2969-10-6617
(01) 07898911288517
Agência Nacional de Telecomunicações

Other manuals for Honeywell TR21-WS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell TR21-WS and is the answer not in the manual?

Honeywell TR21-WS Specifications

General IconGeneral
BrandHoneywell
ModelTR21-WS
CategoryReceiver
LanguageEnglish

Related product manuals