Wiring (continued)
Apply power to TrueDRY DR65. Turn the humidity control to a low RH% level to initiate a dehumidification
call. Confirm that the TrueDRY DR65 compressor and fan turn on. The furnace blower will also turn on to
circulate air. This will take up to two minutes. Be sure to turn the control to the desired RH% or to Off when
checkout is complete. Turning the humidity control to Off will turn TrueDRY DR65 off.
Checkout
M33158
FAN
FURNACE BOARD
EQUIPMENT INTERFACE MODULE (EIM)
G
C
CONV.HP
1
2
3
C
R
RC
RH
W1
W2
W3
Y
Y2
G
O/B
AUX
AUX2
Y
Y2
G
H1
U
M2
D1
H
M2
V1
N
T2
HEAT 1 RELAY
HEAT 2 RELAY
HEAT 3 RELAY
COOL 1 RELAY
COOL 2 RELAY
FAN RELAY
VISIONPRO IAQ
D-1
R-2
C-3
TrueDRY
OR
Gt
+
+
Rf
Gf
EARD-6
DHUM
+
+
R
FAN
C
FLOAT
TrueDry DR65 Dehumidication System 69-2089EFS—12
10
Follow this diagram if using TrueDRY
DR65 with a VisionPro IAQ.