V4044C, V4044F
Motorized Zone Valves
3-PORT HYDRONIC VALVES
Design
V4044C and V4044F zone valves consist of:
3-way valve housing with BSPP internal threads
Control ball assembly
Actuator assembly with cable
V4044F1000 with SPDT end switch
V4044F1034 with SPST end switch
Materials
Valve housing made of forged brass
Spindle shaft made of brass
O-ring seals made of EPDM rubber
Ball plug made of NBR rubber
Actuator cover and base made of zinc-plated steel
Application
Honeywell V4044C and F 3-port hydronic valves are used in
domestic and small commercial heating and cooling
applications to control the flow of hot or cold water.
They are designed for on-off zone control of domestic sys-
tems and can be used to control individual fan coil, radiator,
space heater or convector applications. They can be con-
trolled by a line voltage SPST controller such as a room
thermostat, aquastat or flow switch.
The actuator head is removable without affecting the integrity
of the water system.
Features
Rugged design
Control by a line voltage SPST controller
Actuator head installation does not require draining of
the system
High flow rate capacity
Indifferent to dirt in system
Specifications
Medium Water or water-glycol mixture
(max. 50% glycol content),
quality to VDI 2035
pH-value 8...9.5
Operating temperature 5...88°C (41...190°F)
Ambient temperature max. 50°C (122°F)
Operating pressure max. 8.6 bar (125 psi) static
Differential pressure see chapter “Dimensions” below
k
vs (cv)-values see chapter “Dimensions” below
Flow AB A or B
Starting position port A normally closed
Voltage 220-240V, 50Hz
Power consumption 6W / 0.042A
Auxiliary switch rating 2.2A at 230Vac, 50Hz
Nominal timing On: 30 seconds under power
Off: 12 seconds under spring
return
Electrical termination 1m flying lead, heat resistant
cable
Shipping temperature -40…65°C (-40…149°F)
Humidity rating 5…95% RH (non-condensing)
Atmosphere non-corrosive, non-explosive